B: Application; B1: Operation Mode Selection - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.3 b: Application

12.3
b: Application
b parameters set the following functions.
• Frequency reference source/Run command source
• Stopping method settings
• DC Injection Braking
• Speed Search
• Timer Function
• PID control
• Dwell function
• Droop control
• Energy Savings Control
• Zero Servo Control

b1: Operation Mode Selection

b1 parameters set the operation mode for the drive.
b1-01: Frequency Reference Selection 1
No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
Note:
• Push
on the keypad to set the input mode to LOCAL and enter the frequency reference from the keypad.
• When the drive receives a Run command when the frequency reference is 0 Hz or less than the E1-09 [Minimum Output Frequency] value,
on the keypad will flash. Examine the setting for the frequency reference input and enter a value more than or equal to E1-09.
0 : Keypad
Use the keypad to enter the frequency reference.
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
Use MFAI terminals A1, A2, and A3 to input an analog frequency reference with a voltage or current input signal.
• Voltage Input
Refer to
Table 12.18
to use a voltage signal input to one of the MFAI terminals.
Terminal Signal
Terminal
Level
A1
0 - 10 V
-10 - +10 V
A2
0 - 10 V
-10 - +10 V
A3
0 - 10 V
-10 - +10 V
716
V/f
CL-V/f
OLV
CLV
Sets the input method for the frequency reference.
Table 12.18 Frequency Reference Voltage Input
Parameter Settings
Signal Level
Function Selection
Selection
H3-01 = 0
H3-02 = 0
[Frequency Reference]
H3-01 = 1
H3-09 = 0
H3-10 = 0
[Frequency Reference]
H3-09 = 1
H3-05 = 0
H3-06 = 0
[Frequency Reference]
H3-05 = 1
Description
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Gain
H3-03
H3-11
H3-07
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Setting Range)
1
(0 - 4)
Note
Bias
H3-04
Set DIP switch S1-1 to "V" for
voltage input.
Set DIP switch S1-2 to "V" for
H3-12
voltage input.
Set DIP switch S1-3 to "V" for
H3-08
voltage input.
Set DIP switch S4 to "AI" for
analog input.