YASKAWA GA800 Technical Reference page 613

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

No.
Name
(Hex.)
H7-12
Virtual Multi-Function
Output 2
(11A6)
Expert
H7-13
Virtual Output 2 Delay
Time
(11A7)
Expert
H7-14
Virtual Multi-Function
Output 3
(11A8)
Expert
H7-15
Virtual Output 3 Delay
Time
(11A9)
Expert
H7-16
Virtual Multi-Function
Output 4
(11AA)
Expert
H7-17
Virtual Output 4 Delay
Time
(11AB)
Expert
H7-30
Virtual Analog Input
Selection
(1177)
Expert
H7-31
Virtual Analog Input
Gain
(1178)
RUN
Expert
H7-32
Virtual Analog Input Bias
(1179)
RUN
Expert
H7-40
Virtual Analog Out
Signal Select
(1163)
H7-41
Virtual Analog Output
Function
(1164)
H7-42
Virtual Analog Output
FilterTime
(1165)
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for virtual digital output 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum ON time for virtual digital output 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for virtual digital output 3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum ON time for virtual digital output 3.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for virtual digital output 4.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum ON time for virtual digital output 4.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the virtual analog input function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the virtual analog input gain.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the virtual analog input bias.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level of the virtual analog output.
0 : 0 to 100% (Absolute Value)
1 : -100 to 100%
2 : 0 to 100% (Lower Limit at 0)
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor to be output from the virtual analog output.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H7-41 = 102 to monitor U1-02
[Output Frequency].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time constant for a primary filter of the virtual analog output.
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.10 H: Terminal Functions
Default
Ref.
(Range)
F
955
(0 - 1A7)
0.1 s
955
(0.0 - 25.0 s)
F
955
(0 - 1A7)
0.1 s
955
(0.0 - 25.0 s)
F
956
(0 - 1A7)
0.1 s
956
(0.0 - 25.0 s)
F
956
(0 - 32)
100.0%
956
(-999.9 - 999.9%)
0.0%
956
(-999.9 - 999.9%)
0
956
(0 - 2)
102
956
(0 - 999)
0.00 s
957
(0.00 - 2.00 s)
11
613

Advertisement

Table of Contents
loading

Table of Contents