YASKAWA GA800 Technical Reference page 623

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

No.
Name
(Hex.)
L8-27
Overcurrent Detection
Gain
(04DD)
L8-29
Output Unbalance
Detection Sel
(04DF)
L8-31
LF2 Detection Time
(04E1)
L8-35
Installation Method
Selection
(04EC)
L8-38
Carrier Frequency
Reduction
(04EF)
L8-40
Carrier Freq Reduction
Off-Delay
(04F1)
L8-41
High Current Alarm
Selection
(04F2)
L8-51
STPo I Detection Level
(0471)
Expert
L8-52
STPo Integration Level
(0472)
Expert
L8-53
STPo Integration Time
(0473)
Expert
L8-54
STPo Id Diff Detection
(0474)
Expert
L8-55
Internal DB
TransistorProtection
(045F)
L8-56
Stall P @ Accel
Activation Time
(047D)
Expert
L8-57
Stall Prevention Retry
Counts
(047E)
Expert
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PM motor overcurrent detection level as a percentage of the motor rated current
value.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 ≠ 8 [EZOLV]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8: E9-06 [Motor Rated Current (FLA)]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to detect LF2 [Output Current Imbalance].
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the LF2 [Output Current Imbalance] detection time.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the type of drive installation.
0 : IP20/UL Open Type/Ex Heatsink
1 : Side-by-Side Mounting
2 : IP20/UL Type 1
3 : Finless
V/f
CL-V/f
OLV
CLV
AOLV
Sets the carrier frequency reduction function. The drive reduces the carrier frequency when
the output current is more than a specified level.
0 : Disabled
1 : Enabled below 6 Hz
2 : Enabled for All Speeds
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time until the automatically reduced carrier frequency returns to the
condition before the reduction.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to cause an HCA [Current Alarm] when the output current is more than
150% of the drive rated current.
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the STPo [Motor Step-Out Detected] detection level as a percentage of the motor
rated current.
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the motor
rated current.
• A1-02 = 5 [OLV/PM]: E5-03 [PM Motor Rated Current (FLA)]
• A1-02 = 8 [EZOLV]: E9-06 [Motor Rated Current (FLA)]
V/f
CL-V/f
OLV
CLV
AOLV
Sets the detection level for STPo [Motor Step-Out Detected] related to the ACR integral
value.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time until the drive detects STPo after it is more than the value of L8-51
[STPo I Detection Level].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Id deviation detection function for STPo [Motor Step-Out Detected].
0 : Disabled
1 : Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the protection function for the internal braking transistor.
0 : Disable
1 : Protection Enabled
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length time that the acceleration stall prevention function can continue to operate
before the drive detects an STPo [Motor Step-Out Detected].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of times the acceleration stall prevention function can operate until speeds
agree before the drive detects an STPo [Motor Step-Out Detected].
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.11 L: Protection Functions
Default
Ref.
(Range)
300.0%
1002
(0.0 - 1000.0%)
1
1003
(0, 1)
3
1003
(1 – 100)
Determined by the drive
506
(0 - 3)
Determined by A1-02,
1004
C6-01 and o2-04
(0 - 2)
Determined by A1-02
1004
(0.00 - 2.00 s)
0
1004
(0, 1)
0.0%
1005
(0.0 - 300.0%)
1.0
1005
(0.1 - 2.0)
1.0 s
1005
(1.0 - 10.0 s)
1
1005
(0, 1)
1
1005
(0, 1)
5000 ms
1006
(100 - 5000 ms)
10
1006
(1 - 10 times)
11