H2-62: Terminal M1-M2 Delay Time
No.
Name
(Hex.)
H2-62
Terminal M1-M2 Delay
Time
(1B48)
Expert
H2-63: Term M3-M4 Secondary Function
No.
Name
(Hex.)
H2-63
Term M3-M4 Secondary
Function
(1B49)
Expert
H2-64: Terminal M3-M4 Logical Operation
No.
Name
(Hex.)
H2-64
Terminal M3-M4 Logical
Operation
(1B4A)
Expert
Note:
Refer to
Output of Logical Operation Results of MFDO on page 906
logical operations.
H2-65: Terminal M3-M4 Delay Time
No.
Name
(Hex.)
H2-65
Terminal M3-M4 Delay
Time
(1B4B)
Expert
H2-66: Term M5-M6 Secondary Function
No.
Name
(Hex.)
H2-66
Term M5-M6 Secondary
Function
(1B4C)
Expert
H2-67: Terminal M5-M6 Logical Operation
No.
Name
(Hex.)
H2-67
Terminal M5-M6 Logical
Operation
(1B4D)
Expert
Note:
Refer to
Output of Logical Operation Results of MFDO on page 906
logical operations.
H2-68: Terminal M5-M6 Delay Time
No.
Name
(Hex.)
H2-68
Terminal M5-M6 Delay
Time
(1B4E)
Expert
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum on time used to output the logical calculation results from terminal M1-M2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the second function for terminal M3-M4. Outputs the logical calculation results of the terminals
assigned to functions by H2-02 [Term M3-M4 Function Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the logical operation for the functions set in H2-02 [Term M3-M4 Function Selection] and H2-
63 [Term M3-M4 Secondary Function].
for more information about the relation between parameter settings and
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum on time used to output the logical calculation results from terminal M3-M4.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the second function for terminal M5-M6. Outputs the logical calculation results of the terminals
assigned to functions by H2-03 [Terminal M5-M6 Function Select].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the logical operation for the functions set in H2-03 [Term M5-M6 Function Selection] and H2-
66 [Term M5-M6 Secondary Function].
for more information about the relation between parameter settings and
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum on time used to output the logical calculation results from terminal M5-M6.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 H: Terminal Functions
Default
(Range)
0.1 s
(0.0 - 25.0 s)
Default
(Range)
F
(0 - FF)
Default
(Range)
0
(0 - 8)
Default
(Range)
0.1 s
(0.0 - 25.0 s)
Default
(Range)
F
(0 - FF)
Default
(Range)
0
(0 - 8)
Default
(Range)
0.1 s
(0.0 - 25.0 s)
12