Note:
• It is not available with an SPM motor.
• The speed control range 1:100 is the momentary operation area. When you operate the motor continuously, make sure that the drive
capacity and motor capacity are acceptable.
n8-62: Output Voltage Limit Level
No.
Name
(Hex.)
n8-62
Output Voltage Limit Level
(057D)
Expert
Set this parameter lower than the input power supply voltage.
Note:
• When A1-02 = 7, 8 [Control Method Selection = CLV/PM, EZOLV], this parameter is available in Expert mode.
• When A1-02 = 8 [EZOLV], the default settings are:
–200 V Class: 230.0 V
–400 V Class: 460.0 V
n8-63: Output Voltage Limit P Gain
No.
Name
(Hex.)
n8-63
Output Voltage Limit P Gain
(057E)
Expert
n8-64: Output Voltage Limit I Time
No.
Name
(Hex.)
n8-64
Output Voltage Limit I Time
(057F)
Expert
n8-65: Speed Fdbk Gain @ oV Suppression
No.
Name
(Hex.)
n8-65
Speed Fdbk Gain @ oV
Suppression
(065C)
Expert
Adjust this parameter in these conditions:
• If there is resonance or hunting when you use the overvoltage suppression function, increase the setting value.
• If motor response is low when you use the overvoltage suppression function, decrease the setting value in 0.05-unit
increments.
n8-66: Output Voltage Limit Filter Time
No.
Name
(Hex.)
n8-66
Output Voltage Limit Filter
Time
(0235)
Expert
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the output voltage limit to prevent saturation of the output voltage. Usually it is not necessary to
change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the proportional gain for output voltage control. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the integral time for output voltage control. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain of internal speed feedback detection suppression while the overvoltage suppression
function is operating as a magnification value. Usually it is not necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the filter time constant for output voltage control. Usually it is not necessary to change this
setting.
12.10 n: Special Adjustment
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
200 V Class: 200.0 V,
400 V Class: 400.0 V
(200 V Class: 0.0 to 240.0 V,
400 V Class: 0.0 to 480.0 V)
Default
(Range)
1.00
(0.00 - 100.00)
Default
(Range)
0.040 s
(0.000 - 5.000)
Default
(Range)
1.50
(0.00 - 10.00)
Default
(Range)
0.020 s
(0.000 - 5.000)
12
1031