YASKAWA GA800 Technical Reference page 956

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.8 H: Terminal Functions
H7-16: Virtual Multi-Function Output 4
No.
Name
(Hex.)
H7-16
Virtual Multi-Function
Output 4
(11AA)
Expert
H7-17: Virtual Output 4 Delay Time
No.
Name
(Hex.)
H7-17
Virtual Output 4 Delay Time
(11AB)
Expert
H7-30: Virtual Analog Input Selection
No.
Name
(Hex.)
H7-30
Virtual Analog Input
Selection
(1177)
Expert
H7-31: Virtual Analog Input Gain
No.
Name
(Hex.)
H7-31
Virtual Analog Input Gain
(1178)
RUN
Expert
H7-32: Virtual Analog Input Bias
No.
Name
(Hex.)
H7-32
Virtual Analog Input Bias
(1179)
RUN
Expert
H7-40: Virtual Analog Out Signal Select
No.
Name
(Hex.)
H7-40
Virtual Analog Out Signal
Select
(1163)
0 : 0 to 100% (Absolute Value)
1 : -100 to 100%
2 : 0 to 100% (Lower Limit at 0)
H7-41: Virtual Analog Output Function
No.
Name
(Hex.)
H7-41
Virtual Analog Output
Function
(1164)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H7-41 = 102 to monitor U1-02 [Output Frequency].
956
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function for virtual digital output 4.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum ON time for virtual digital output 4.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the virtual analog input function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the virtual analog input gain.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the virtual analog input bias.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level of the virtual analog output.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor to be output from the virtual analog output.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
F
(0 - 1A7)
Default
(Range)
0.1 s
(0.0 - 25.0 s)
Default
(Range)
F
(0 - 32)
Default
(Range)
100.0%
(-999.9 - 999.9%)
Default
(Range)
0.0%
(-999.9 - 999.9%)
Default
(Range)
0
(0 - 2)
Default
(Range)
102
(0 - 999)