E5: Pm Motor Settings - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

E4-10: Motor 2 Iron Loss
No.
Name
(Hex.)
E4-10
Motor 2 Iron Loss
(0340)
E4-11: Motor 2 Rated Power
No.
Name
(Hex.)
E4-11
Motor 2 Rated Power
(0327)
Auto-Tuning automatically sets this parameter to the value input for [Motor Rated Power].

E5: PM Motor Settings

E5 parameters are used to set PM motor data.
Set E5-01 to the motor code when using PM motors recommended by Yaskawa. E5 and other related motor
parameters will be automatically set to the optimal values.
Perform Auto-Tuning for all other PM motors. If information from motor nameplates or test reports is available, the
E5 parameters can be manually entered.
Note:
• The keypad displays E5-xx only when A1-02 = 5, 6, 7 [Control Method Selection = OLV/PM, AOLV/PM, CLV/PM].
• E5-xx parameters are not reset when the drive is initialized using parameter A1-03 [Initialize Parameters].
E5-01: PM Motor Code Selection
No.
Name
(Hex.)
E5-01
PM Motor Code Selection
(0329)
Note:
If the drive hunts or shows an alarm after you enter a motor code, use the keypad to enter the value shown on the nameplate to E5-xx.
E5-02: PM Motor Rated Power
No.
Name
(Hex.)
E5-02
PM Motor Rated Power
(032A)
The drive will automatically set this parameter the next time you do Auto-Tuning.
• PM Motor Parameter Settings
• PM Stationary Auto-Tuning
• PM Rotational Auto-Tuning
E5-03: Motor Rated Current (FLA)
No.
Name
(Hex.)
E5-03
Motor Rated Current (FLA)
(032B)
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor iron loss for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor rated power in the units from o1-58 [Motor Power Unit Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor code for Yaskawa PM motors. The drive uses the motor code to automatically set
some parameters to their correct settings.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PM motor rated output in the units set in o1-58 [Motor Power Unit Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the PM motor rated current (FLA).
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.6 E: Motor Parameters
Default
(Range)
Determined by o2-04, C6-01
(0 - 65535 W)
Default
(Range)
Determined by o2-04, C6-01
(0.00 - 650.00 HP)
Default
(Range)
FFFF
(0000 - FFFF)
Default
(Range)
Determined by o2-04, C6-01
(0.10 - 650.00 HP)
Default
(Range)
Determined by E5-01
(10% to 200% of the drive
rated current)
833