YASKAWA GA800 Technical Reference page 474

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

8.5 Replace the Drive
Connect the Control Circuit Terminal Block
1.
To put a wired control circuit terminal block in the drive, align it with the guides and move it straight up.
A - Guides
2.
Use M3 screws to safety the terminal block.
Tighten the screws to a correct tightening torque:
• M3 screws: 0.5 N∙m to 0.6 N∙m (4.4 lbf∙in to 5.3 lbf∙in)
3.
Install the front cover and the keypad to their initial positions.
4.
Check o2-04 [Drive Model (KVA) Selection].
Note:
• When you save parameter information in a keypad that you installed before you replaced the terminal block, make sure that you use that
keypad to restore the parameter data.
• To reset the performance life monitors for the components, set o4-01 to o4-13 [Maintenance Period].
474
Figure 8.94 Put the Terminal Block into the Connector
Figure 8.95 Safety the Terminal Block
YASKAWA SIEPC71061737D GA800 Drive Technical Reference