YASKAWA GA800 Technical Reference page 915

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

OFF : Output frequency ≥ value of E1-09 or b2-01.
2: Speed Agree 1
Setting Value
Function
2
Speed Agree 1
Note:
• The detection function operates in the two motor rotation directions.
• The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-
72 = 1.
ON : The output frequency is in the range of "frequency reference ± L4-02".
OFF : The output frequency does not align with the frequency reference although the drive is
running.
3: User-Set Speed Agree 1
Setting Value
Function
3
User-Set Speed Agree 1
Note:
• The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the forward/reverse detection level.
• The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed status when A1-02 = 4 and n4-
72 = 1.
ON : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ±
L4-02.
OFF : The output frequency is not in the range of "L4-01 ± L4-02" or the range of frequency
reference ± L4-02.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
The terminal turns on when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree Detection Width].
Figure 12.91 Speed Agree 1 Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02 [Speed Agree
Detection Width] and in the range of the frequency reference ± L4-02.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 H: Terminal Functions
12
915

Advertisement

Table of Contents
loading

Table of Contents