3: Auxiliary Frequency Reference 2
Setting Value
Function
3
Auxiliary Frequency
Reference 2
4: Output Voltage Bias
Setting Value
Function
4
Output Voltage Bias
The gain (%) for the MFAI terminals A1, A2, and A3 is 100% of the voltage class standard, which is 200 V for 200 V
class drives and 400 V for 400 V class drives. The bias (%) for MFAI terminals A1, A2, and A3 is 100% of the
voltage configured for E1-05 [Maximum Output Voltage].
Note:
The gain for each terminal A1, A2, and A3 is configured independently with H3-03 [Terminal A1 Gain Setting], H3-11 [Terminal A2 Gain
Setting], and H3-07 [Terminal A3 Gain Setting]. The bias for each terminal A1, A2, and A3 is configured independently with H3-04
[Terminal A1 Bias Setting], H3-12 [Terminal A2 Bias Setting], and H3-08 [Terminal A3 Bias Setting].
5: Accel/Decel Time Gain
Setting Value
Function
5
Accel/Decel Time Gain
When you enable C1-01 [Acceleration Time 1], the acceleration time is:
Acceleration Time 1 = Setting value of C1-01 × acceleration and deceleration time gain / 100
Figure 12.105 Acceleration/Deceleration Time Gain through Analog Input
6: DC Injection Braking Current
Setting Value
Function
6
DC Injection Braking
Current
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets Reference 3 through multi-step speed reference to enable the command reference (Auxiliary Frequency Reference 2) from the
analog input terminal set here. This value is a percentage where the Maximum Output Frequency setting is a setting value of 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Set this parameter to input a bias signal and amplify the output voltage.
Figure 12.104 Output Voltage Bias through Analog Input
V/f
CL-V/f
OLV
CLV
AOLV
Enters a signal to adjust the gain used for C1-01 to C1-08 [Acceleration/Deceleration Times 1 to 4] and C1-09 [Fast Stop Time]
when the full scale analog signal (10 V or 20 mA) is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters a signal to adjust the current level used for DC Injection Braking when the drive rated output current is 100%.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 H: Terminal Functions