YASKAWA GA800 Technical Reference page 888

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.8 H: Terminal Functions
9: Baseblock Command (N.C.)
Setting Value
Function
9
Baseblock Command (N.C.)
The keypad flashes bb [Baseblock]. If you cancel the baseblock command when the Run command is active, the drive
will restart the motor and use the speed search function.
ON : Normal operation
OFF : Baseblock (drive output stop)
A: Accel/Decel Ramp Hold
Setting Value
Function
A
Accel/Decel Ramp Hold
If the terminal is deactivated, the drive restarts acceleration and deceleration.
When the acceleration/deceleration ramp hold terminal is activated and d4-01 = 1 [Freq Reference Retention Select =
Enabled], the drive will store the output frequency in memory. While the acceleration/deceleration ramp hold
command is activated, the drive will always restart the motor at this output frequency.
Note:
Refer to
d4-01: Freq Reference Hold Selection on page 804
B: Overheat Alarm (oH2)
Setting Value
Function
B
Overheat Alarm (oH2)
C: Analog Terminal Enable Selection
Setting Value
Function
C
Analog Terminal Enable
Selection
ON : Terminal selected with H3-14 is enabled
OFF : Terminal selected with H3-14 is disabled
D: Ignore Speed Fdbk (V/f w/o Enc)
Setting Value
Function
D
Ignore Speed Fdbk (V/f w/o
Enc)
ON : Speed feedback control disable (V/f Control)
OFF : Speed feedback control enable (Closed Loop V/f Control)
E: ASR Integral Reset
Setting Value
Function
E
ASR Integral Reset
ON : P control
OFF : PI control
888
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command that stops drive output and coasts the motor to stop when the input terminal is OFF.
V/f
CL-V/f
OLV
CLV
AOLV
Momentarily pauses motor acceleration and deceleration when the terminal is turned ON, retains the output frequency that was
stored in the drive at the time of the pause, and restarts motor operation.
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive to show an oH2 [External Overheat (H1-XX=B)] alarm when the input terminal is ON. The alarm does not have an
effect on drive operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command that enables or disables the terminals selected in H3-14 [Analog Input Terminal Enable Sel].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to disable speed feedback control and run the drive in V/f control or use speed feedback from the encoder.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the command to reset the integral value and use PI control or P control for the speed control loop.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference

Advertisement

Table of Contents
loading

Table of Contents