Note:
When you use L7-01 to L7-04 and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
12: Regenerative Torque Limit
Setting Value
Function
12
Regenerative Torque Limit
Note:
When you use L7-01 to L7-04 and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
13: Torque Reference / Torque Limit
Setting Value
Function
13
Torque Reference / Torque
Limit
Note:
When you use L7-01 to L7-04 and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
14: Torque Compensation
Setting Value
Function
14
Torque Compensation
15: General Torque Limit
Setting Value
Function
15
General Torque Limit
16: Differential PID Feedback
Setting Value
Function
16
Differential PID Feedback
The drive uses the deviation between the PID feedback and the differential feedback value signals to calculate the PID
input.
1F: Not Used
Setting Value
Function
1F
Not Used
When you set a terminal that you do not use to 1F, you can use the signal that is input to that terminal as the PLC
analog signal input from MEMOBUS/Modbus communications or the communication option. This input signal does
not have an effect on drive operation. This signal functions the same as F (Through Mode).
30: DWEZ Analog Input 1
Setting Value
Function
30
DWEZ Analog Input 1
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Enters the regenerative torque limit if the motor rated torque is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters the torque reference if the motor rated torque is 100%. This setting is the torque limit for speed control.
V/f
CL-V/f
OLV
CLV
AOLV
Enters the torque compensation value if the motor rated torque is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative operation if the motor rated torque is
100%.
V/f
CL-V/f
OLV
CLV
AOLV
Enters the PID differential feedback value if the full scale analog signal (10 V or 20 mA) is 100%.
V/f
CL-V/f
OLV
CLV
AOLV
Use this setting for unused terminals or to use terminals in through mode.
V/f
CL-V/f
OLV
CLV
AOLV
Use with DriveWorksEZ. Refer to the DriveWorksEZ online manual for more information.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
12.8 H: Terminal Functions
12
941