A: Initialization Parameters; A1: Initialization - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

11.4 A: Initialization Parameters

11.4
A: Initialization Parameters

A1: Initialization

No.
Name
(Hex.)
A1-00
Language Selection
(0100)
RUN
A1-01
Access Level Selection
(0101)
RUN
A1-02
Control Method Selection
(0102)
A1-03
Initialize Parameters
(0103)
A1-04
Password
(0104)
A1-05
Password Setting
(0105)
A1-06
Application Preset
(0127)
538
V/f
CL-V/f
OLV
CLV
AOLV
Sets the language for the LCD keypad.
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will not
reset this parameter.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
V/f
CL-V/f
OLV
CLV
AOLV
Sets user access to parameters. The access level controls which parameters the keypad will
display, and which parameters the user can set.
0 : Operation Only
1 : User Parameters
2 : Advanced Level
3 : Expert Level
V/f
CL-V/f
OLV
CLV
AOLV
Sets the control method for the drive application and the motor.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
4 : Advanced Open Loop Vector
5 : PM Open Loop Vector
6 : PM Advanced Open Loop Vector
7 : PM Closed Loop Vector
8 : EZ Vector Control
V/f
CL-V/f
OLV
CLV
AOLV
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
3330 : 3-Wire Initialization
V/f
CL-V/f
OLV
CLV
AOLV
Entry point for the password set in A1-05 [Password Setting]. The user can view the
settings of parameters that are locked without entering the password. Enter the correct
password in this parameter to change parameter settings.
V/f
CL-V/f
OLV
CLV
AOLV
Set the password to lock parameters and prevent changes to parameter settings. Enter the
correct password in A1-04 [Password] to unlock parameters and accept changes.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive to operate in selected application conditions.
0 : General-purpose
1 : Water Supply Pump 2
2 : Conveyor
3 : Exhaust Fan
4 : HVAC Fan
5 : Air Compressor
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
Ref.
(Range)
0
697
(0 - 12)
2
697
(0 - 3)
2
698
(0 - 8)
0
699
(0 - 3330)
0000
700
(0000 - 9999)
0000
701
(0000 - 9999)
0
701
(0 - 5)

Advertisement

Table of Contents
loading

Table of Contents