C5-38: Motor 2 Load Inertia Ratio
No.
Name
(Hex.)
C5-38
Motor 2 Load Inertia Ratio
(0279)
Expert
The drive automatically sets C5-38 to the value of [Load Inertia Ratio] when you do Inertia Tuning or ASR Tuning.
C5-39: ASR Primary Delay Time Const 2
No.
Name
(Hex.)
C5-39
ASR Primary Delay Time
Const 2
(030D)
If you have a load with low rigidity or if oscillation is a problem, increase this setting in 0.01 unit increments.
C5-50: Notch Filter Frequency
No.
Name
(Hex.)
C5-50
Notch Filter Frequency
(0B14)
Expert
Machine resonance can cause high-frequency noise and vibration during operation. A notch filter can help prevent the
noise and vibration. Notch filters set the resonant frequency of the machine to remove specific vibrational frequency
components caused by machine resonance.
Note:
• Correctly set the value for the notch filter frequency. If the frequency value is too low for the speed loop response frequency, the speed
control function will not function correctly. Set the frequency to be a minimum of 4 times the speed loop response frequency.
• Set C5-50 = 0 [0 Hz] to disable the notch filter.
C5-51: Notch Filter Bandwidth
No.
Name
(Hex.)
C5-51
Notch Filter Bandwidth
(0B15)
Expert
Note:
Set C5-50 = 0 [Notch Filter Frequency = 0 Hz] to disable the notch filter.
C6: Duty & Carrier Frequency
C6 parameters are used to set the selection of drive duty rating, selection of carrier frequency, and upper and lower
limits of carrier frequencies.
C6-01: Normal / Heavy Duty Selection
No.
Name
(Hex.)
C6-01
Normal / Heavy Duty
Selection
(0223)
0 : Heavy Duty Rating
The overload tolerance is 150% of the rated output current for 60 seconds.
1 : Normal Duty Rating
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the load inertia ratio for the motor 2 inertia.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the filter time constant used when the torque reference is output from ASR. Usually it is not
necessary to change this parameter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the machine resonance frequency.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the notch width of the notch filter.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive duty rating.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.4 C: Tuning
Default
(Range)
1.0
(0.0 - 6000.0)
Default
(Range)
0.000 s
(0.000 - 0.500 s)
Default
(Range)
0 Hz
(0, or 2 to 100 Hz)
Default
(Range)
1.0
(0.5 - 5.0)
Default
(Range)
1
(0, 1)
12
791