YASKAWA GA800 Technical Reference page 984

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.9 L: Protection Functions
L3-34: Torque Limit Delay Time
No.
Name
(Hex.)
L3-34
Torque Limit Delay Time
(016F)
Expert
When vibration occurs during operation of Single Drive KEB Ride-Thru 2, increase this parameter in 0.010-unit
increments.
Note:
The Single Drive KEB Ride-Thru 2 mode operates when L2-29 = 1 [KEB Method Selection = Single Drive KEB Ride-Thru 2] and H1-xx =
7A or 7B [Terminal Sx Function Selection = KEB Ride-Thru 2 (N.C./N.O.)].
L3-35: Speed Agree Width for Auto Decel
No.
Name
(Hex.)
L3-35
Speed Agree Width for Auto
Decel
(0747)
Expert
Set this parameter when hunting occurs while you use a frequency reference through an analog input.
L3-36: Current Suppression Gain@Accel
No.
Name
(Hex.)
L3-36
Current Suppression
Gain@Accel
(11D0)
If there is vibration in the output current during acceleration, increase the setting value.
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Method] to enable this function.
L3-37: Current Limit P Gain @ Accel
No.
Name
(Hex.)
L3-37
Current Limit P Gain @
Accel
(11D1)
Expert
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Method] to enable this function.
L3-38: Current Limit I Time @ Accel
No.
Name
(Hex.)
L3-38
Current Limit I Time @
Accel
(11D2)
Expert
Note:
Set L3-01 = 3 [Stall Prevention during Accel = Current Limit Method] to enable this function.
984
V/f
CL-V/f
OLV
CLV
AOLV
Sets the filter time constant that returns the torque limit to its initial value when KEB operation
operates in Single Drive KEB Ride-Thru mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the width for speed agreement when L3-04 = 2 [Stall Prevention during Decel = Intelligent
(Ignore Decel Ramp)]. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain to suppress current and motor speed hunting during operation when L3-01 = 3 [Stall
Prevention during Accel = Current Limit Method]. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Suppresses current hunting during acceleration. Usually it is not necessary to change this setting.
V/f
CL-V/f
OLV
CLV
AOLV
Suppresses current hunting and overshooting that occurs when the drive stalls during acceleration.
Usually it is not necessary to change this setting.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
Determined by A1-02
(0.000 - 1.000 s)
Default
(Range)
0.00 Hz
(0.00 - 1.00 Hz)
Default
(Range)
Determined by A1-02
(0.0 - 100.0)
Default
(Range)
5 ms
(0 - 100 ms)
Default
(Range)
10.0
(0.0 - 100.0)

Advertisement