12.9 L: Protection Functions
Note:
The default setting and setting range is different for different models.
• 200 V Class and 400 V Class
Default: 1
Setting range: 0, 1
• 6-Phase/12-Pulse 400 V Class
Default: 4
Setting range: 0 - 4
The software version for 6-Phase/12-Pulse drive is PRG: 09015 and later. The "PRG" column on the nameplate on the right side of the drive
identifies the software version. You can also use U1-25 [SoftwareNumber Flashr] to identify the software version.
0 : Disable
1 : Enabled
The drive measures ripples in DC bus voltage to detect input phase loss.
The drive detects phase loss when power supply phase loss occurs or the main circuit capacitor becomes unusable,
which causes PF [Input Phase Loss] to show on the keypad.
Disable the detection of the input power supply phase loss function in these conditions:
• During deceleration
• The run command is not input
• The output current is less than 30% of the drive rated current.
4 : Enabled, with Hardware Detection
L8-07: Output Phase Loss Protection Sel
No.
Name
(Hex.)
L8-07
Output Phase Loss
Protection Sel
(04B3)
Note:
The drive can incorrectly start output phase loss detection in these conditions:
• The motor rated current is very small compared to the drive rating.
• The drive is operating a PM motor with a small load.
0 : Disabled
1 : Fault when one phase is lost
If the drive loses one output phase, it will trigger LF [Output Phase Loss].
The output turns off and the motor coasts to stop.
2 : Fault when two phases are lost
If the drive loses more than one output phase, it will trigger LF [Output Phase Loss].
The output turns off and the motor coasts to stop.
L8-09: Output Ground Fault Detection
No.
Name
(Hex.)
L8-09
Output Ground Fault
Detection
(04B5)
0 : Disabled
The drive will not detect ground faults.
1 : Enabled
If there is high leakage current or a ground short circuit in one or two output phases, the drive will detect GF [Ground
Fault].
Note:
If the ground path impedance is low, the drive can detect oC [Overcurrent], SC [Short Circuit/IGBT Failure], or ov [Overvoltage] instead of
GF.
1000
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable and disable output phase loss detection. The drive starts output phase loss
detection when the output current decreases to less than 5% of the drive rated current.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to enable and disable ground fault protection.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
1
(0 - 2)
Default
(Range)
Determined by o2-04
(0, 1)