ON : The output frequency is higher than the value of L4-03.
OFF : The output frequency is less than the value of "L4-03 - L4-04", or it is not higher than the value
of L4-03.
Figure 12.98 Example of Frequency Detection 4 (value of L4-03 Is Positive)
17: Torque Detection 1 (N.C.)
Setting Value
Function
17
Torque Detection 1 (N.C.)
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than L6-02 [Torque Detection Level 1], or the level is less
than L6-02 for longer thanL6-03 [Torque Detection Time 1].
Note:
• When L6-01 ≥ 5, the drive will detect when the output current/torque is less than L6-02 for longer than L6-03.
• Refer to
L6: Torque Detection on page 989
18: Torque Detection 2 (N.O.)
Setting Value
Function
18
Torque Detection 2 (N.O.)
Use the L6 [Torque Detection] parameters to set torque detection.
ON : The output current/torque is more than L6-05 [Torque Detection Level 2], or the level is less
than L6-05 for longer thanL6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.
• Refer to
L6: Torque Detection on page 989
19: Torque Detection 2 (N.C.)
Setting Value
Function
19
Torque Detection 2 (N.C.)
Use the L6 [Torque Detection] parameters to set torque detection.
OFF : The output current/torque is more than L6-05 [Torque Detection Level 2], or the level is less
than L6-05 for longer than L6-06 [Torque Detection Time 2].
Note:
• When L6-04 ≥ 5, the drive will detect when the output current/torque is less than L6-05 for longer than L6-06.
• Refer to
L6: Torque Detection on page 989
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects overtorque or undertorque.
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal deactivates when the drive detects overtorque or undertorque.
for more information.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 H: Terminal Functions
12
921

Advertisement

Table of Contents
loading

Table of Contents