YASKAWA GA800 Technical Reference page 935

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

H3-16: Terminal A1 Offset
No.
Name
(Hex.)
H3-16
Terminal A1 Offset
(02F0)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-01= 2] or 0 mA [H3-01 = 3]
is input.
H3-17: Terminal A2 Offset
No.
Name
(Hex.)
H3-17
Terminal A2 Offset
(02F1)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-09 = 2] or 0 mA [H3-09 =
3] is input.
H3-18: Terminal A3 Offset
No.
Name
(Hex.)
H3-18
Terminal A3 Offset
(02F2)
Adds the offset value for the analog input value. For voltage input, this parameter will set the offset when a signal of 0
V is input. For current input, this parameter will set the offset when a signal of 4 mA [H3-05 = 2] or 0 mA [H3-05 =
3] is input.
H3-40: Mbus Reg 15C1h Input Function
No.
Name
(Hex.)
H3-40
Mbus Reg 15C1h Input
Function
(0B5C)
You can use the MFAI function from MEMOBUS/Modbus communications. Use this parameter to set the function.
Sets the function for MEMOBUS/Modbus register 15C1h.
Refer to
Multi-Function Analog Input Terminal Settings on page 936
H3-41: Mbus Reg 15C2h Input Function
No.
Name
(Hex.)
H3-41
Mbus Reg 15C2h Input
Function
(0B5F)
You can use the MFAI function from MEMOBUS/Modbus communications. Use this parameter to set the function.
Sets the function for MEMOBUS/Modbus register 15C2h.
Refer to
Multi-Function Analog Input Terminal Settings on page 936
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A1. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A2. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the offset level for analog signals input to terminal A3. Usually it is not necessary to change this
setting.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MEMOBUS AI1 function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MEMOBUS AI2 function.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
for the setting values.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
for the setting values.
12.8 H: Terminal Functions
Default
(Range)
0
(-500 - +500)
Default
(Range)
0
(-500 - +500)
Default
(Range)
0
(-500 - +500)
Default
(Range)
F
(4 - 2F)
Default
(Range)
F
(4 - 2F)
12
935