11.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
*6
The maximum value changes when A1-02 changes:
• When A1-02 = 5 [PM Open Loop Vector], the maximum value is 590.0 Hz. The maximum value of the setting range changes when E5-
01 [PM Motor Code Selection] changes. When E5-01 = FFFF [PM Motor Code Selection = FFFF], the maximum value is 590.0 Hz.
• When A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector], the maximum value is 400.0 Hz. The maximum
value of the setting range changes when E5-01 changes. When E5-01 = FFFF, the maximum value is 400.0 Hz.
*7
This is the value for 200 V class drives. Double the value for 400 V class drives.
*8
The default setting changes when E9-01 [Motor Type Selection] changes.
• E9-01 = 0 [Induction (IM)]: 1
• E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 4
*9
The default setting changes when E9-01 [Motor Type Selection] changes.
• E9-01 = 0 [Induction (IM)]: 0
• E9-01 = 1, 2 [Permanent Magnet (PM), Synchronous Reluctance (SynRM)]: 1
*10 The maximum value changes when A1-02 changes:
• When A1-02 = 5 [PM Open Loop Vector], the maximum value is 590.0 Hz.
• When A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector], the maximum value is 100.0%.
• When A1-02 = 8 [EZ Vector Control], the maximum value is 120.0 Hz.
*11 The minimum value changes when A1-02 changes:
• When A1-02 = 5 [PM Open Loop Vector], the minimum value is -590.0 Hz.
• When A1-02 = 6 or 7 [PM Advanced Open Loop Vector or PM Closed Loop Vector], the minimum value is -100.0%.
• When A1-02 = 8 [EZ Vector Control], the minimum value is -120.0 Hz.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
11