E2-04: Motor Pole Count
No.
Name
(Hex.)
E2-04
Motor Pole Count
(0311)
Note:
• When A1-02 = 0, 1, 3 [Control Method Selection = V/f, CL-V/f, CLV], the maximum value is 120.
• When A1-02 = 2, 4 [OLV, AOLV], the maximum value is 48.
Auto-Tuning automatically sets this parameter to the value of [Number of Motor Poles].
E2-05: Motor Line-to-Line Resistance
No.
Name
(Hex.)
E2-05
Motor Line-to-Line
Resistance
(0312)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the resistance per phase.
Auto-Tuning automatically sets this parameter. If you cannot do Auto-Tuning, use the test report from the motor
manufacturer to configure the settings. You can calculate the motor line-to-line resistance with one of these formulas:
• E-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.822
• B-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.822
• F-type insulation: [the resistance value (Ω) shown on the test report at 115 °C] × 0.728
E2-06: Motor Leakage Inductance
No.
Name
(Hex.)
E2-06
Motor Leakage Inductance
(0313)
The drive automatically sets this parameter during Auto-Tuning.
Note:
The motor nameplate does not usually show the quantity of voltage drop. If you do not know the value of the motor leakage inductance,
contact the motor manufacturer to receive a copy of the motor test report.
E2-07: Motor Saturation Coefficient 1
No.
Name
(Hex.)
E2-07
Motor Saturation Coefficient
1
(0314)
The drive uses this coefficient when it operates with constant output. The drive uses this coefficient when it operates
the motor in the constant output range.
E2-08: Motor Saturation Coefficient 2
No.
Name
(Hex.)
E2-08
Motor Saturation Coefficient
2
(0315)
The drive uses this coefficient when it operates with constant output. The drive uses this coefficient when it operates
the motor in the constant output range.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the number of motor poles.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the line-to-line resistance for the motor stator windings.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the voltage drop from motor leakage inductance when the motor is operating at the rated
frequency and rated current. This value is a percentage of Motor Rated Voltage.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor iron-core saturation coefficient at 50% of the magnetic flux.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the motor iron-core saturation coefficient at 75% of the magnetic flux.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.6 E: Motor Parameters
Default
(Range)
4
(2 - 120)
Default
(Range)
Determined by o2-04, C6-01
(0.000 - 65.000 Ω)
Default
(Range)
Determined by o2-04, C6-01
(0.0 - 60.0%)
Default
(Range)
0.50
(0.00 - 0.50)
Default
(Range)
0.75
(E2-07 - 0.75)