12.8 H: Terminal Functions
H2-36: Comparator 1 Ineffective Time
No.
Name
(Hex.)
H2-36
Comparator 1 Ineffective
Time
(159E)
Note:
• After you enter a Run command and wait for the time set in this parameter, the drive will monitor operation and make sure that it is in the
Comparator 1 range until you enter the Stop command.
• When CP1 detection is disabled, the drive will activate the output terminal set for Comparator 1 [H2-xx = 66].
H2-37: Comparator 2 Ineffective Time
No.
Name
(Hex.)
H2-37
Comparator 2 Ineffective
Time
(159F)
Note:
• After you enter a Run command and wait for the time set in this parameter, the drive will monitor operation and make sure that it is in the
Comparator 2 range until you enter the Stop command.
• When CP2 detection is disabled, the drive will activate the output terminal set for Comparator 2 [H2-xx = 67].
H2-40: Mbus Reg 15E0h bit0 Output Func
No.
Name
(Hex.)
H2-40
Mbus Reg 15E0h bit0
Output Func
(0B58)
H2-41: Mbus Reg 15E0h bit1 Output Func
No.
Name
(Hex.)
H2-41
Mbus Reg 15E0h bit1
Output Func
(0B59)
H2-42: Mbus Reg 15E0h bit2 Output Func
No.
Name
(Hex.)
H2-42
Mbus Reg 15E0h bit2
Output Func
(0B5A)
H2-60: Term M1-M2 Secondary Function
No.
Name
(Hex.)
H2-60
Term M1-M2 Secondary
Function
(1B46)
Expert
H2-61: Terminal M1-M2 Logical Operation
No.
Name
(Hex.)
H2-61
Terminal M1-M2 Logical
Operation
(1B47)
Expert
Note:
Refer to
Output of Logical Operation Results of MFDO on page 906
logical operations.
912
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that CP1 [Comparator1 Limit Fault] is disabled.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that CP2 [Comparator2 Limit Fault] is disabled.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MFDO for bit 0 of MEMOBUS register 15E0 (Hex.).
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MFDO for bit 1 of MEMOBUS register 15E0 (Hex.).
V/f
CL-V/f
OLV
CLV
AOLV
Sets the MFDO for bit 2 of MEMOBUS register 15E0 (Hex.).
V/f
CL-V/f
OLV
CLV
AOLV
Sets the second function for terminal M1-M2. Outputs the logical calculation results of the terminals
assigned to functions by H2-01 [Term M1-M2 Function Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the logical operation for the functions set in H2-01 [Term M1-M2 Function Selection] and H2-
60 [Term M1-M2 Secondary Function].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
for more information about the relation between parameter settings and
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
0.0 s
(0.0 - 1000.0 s)
Default
(Range)
0.0 s
(0.0 - 1000.0 s)
Default
(Range)
F
(0 - 1FF)
Default
(Range)
F
(0 - 1FF)
Default
(Range)
F
(0 - 1FF)
Default
(Range)
F
(0 - FF)
Default
(Range)
0
(0 - 8)