12.8 H: Terminal Functions
A - H2-24
[Comparator 1 On-Delay Time]
Note:
The drive compares the monitors set with H2-20 as absolute values.
67: Comparator2
Setting Value
Function
67
Comparator2
A - H2-30
[Comparator 2 On-Delay Time]
Note:
The drive compares the monitors set with H2-26 as absolute values.
69: External Power 24V Supply
Setting Value
Function
69
External Power 24V Supply
ON : The external 24V power supply is supplying power.
OFF : The external 24V power supply is not supplying power.
928
Figure 12.101 Comparator 1 Output Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of the values of H2-
27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-30 [Comparator 2 On-Delay Time].
Figure 12.102 Comparator 2 Output Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when there is an external 24V power supply between terminals PS-AC.
B - H2-25
[Comparator 1 Off-Delay Time]
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
B - H2-31
[Comparator 2 Off-Delay Time]
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference