H2-21: Comparator 1 Lower Limit
No.
Name
(Hex.)
H2-21
Comparator 1 Lower Limit
(1541)
Note:
For information on the comparator function, refer to
H2-22: Comparator 1 Upper Limit
No.
Name
(Hex.)
H2-22
Comparator 1 Upper Limit
(1542)
Note:
For information on the comparator function, refer to
H2-23: Comparator 1 Hysteresis
No.
Name
(Hex.)
H2-23
Comparator 1 Hysteresis
(1543)
Note:
For information on the comparator function, refer to
H2-24: Comparator 1 On-Delay Time
No.
Name
(Hex.)
H2-24
Comparator 1 On-Delay
Time
(1544)
Note:
For information on the comparator function, refer to
H2-25: Comparator 1 Off-Delay Time
No.
Name
(Hex.)
H2-25
Comparator 1 Off-Delay
Time
(1545)
Note:
For information on the comparator function, refer to
H2-26: Comparator 2 Monitor Selection
No.
Name
(Hex.)
H2-26
Comparator 2 Monitor
Selection
(1546)
Note:
• The configurable monitor changes when the control method changes.
• When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal output level from the PLC through
MEMOBUS/Modbus communications or the communication option.
• For information on the comparator function, refer to
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the lower limit detection level for comparator 1 when the full scale analog output for the monitor
selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
66: Comparator1 on page 927
V/f
CL-V/f
OLV
CLV
AOLV
Sets the upper limit detection level for comparator 1 when the full scale analog output for the monitor
selected in H2-20 [Comparator 1 Monitor Selection] is the 100% value.
66: Comparator1 on page 927
V/f
CL-V/f
OLV
CLV
AOLV
Sets the hysteresis level for comparator 1 as a percentage of the full scale analog output for the
monitor selected in H2-20 [Comparator 1 Monitor Selection].
66: Comparator1 on page 927
V/f
CL-V/f
OLV
CLV
AOLV
Sets the on-delay time for comparator 1.
66: Comparator1 on page 927
V/f
CL-V/f
OLV
CLV
AOLV
Sets the off-delay time for comparator 1.
66: Comparator1 on page 927
V/f
CL-V/f
OLV
CLV
AOLV
Sets the monitor number for comparator 2. Set the x-xx part of the Ux-xx [Monitor]. For example, set
H2-26 = 103 to monitor U1-03 [Output Current].
66: Comparator1 on page 927
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
and
67: Comparator2 on page
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
and
67: Comparator2 on page
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
and
67: Comparator2 on page
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
and
67: Comparator2 on page
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
and
67: Comparator2 on page
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
and
67: Comparator2 on page
12.8 H: Terminal Functions
Default
(Range)
0.0%
(0.0 - 300.0%)
928.
Default
(Range)
0.0%
(0.0 - 300.0%)
928.
Default
(Range)
0.0%
(0.0 - 10.0%)
928.
Default
(Range)
0.0 s
(0.0 - 600.0 s)
928.
Default
(Range)
0.0 s
(0.0 - 600.0 s)
928.
Default
(Range)
103
(000 - 999)
928.
12
909