YASKAWA GA800 Technical Reference page 763

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

• Set parameters b8-16, b8-17 when using a PM motor.
Note:
• Energy-saving control is not appropriate for applications with sudden changes in the load, or applications driving heavy loads such as a
traverse car application.
• Energy-saving control maximizes operation based on precise motor data set to the drive. Be sure to perform Auto-Tuning and enter the
correct information about the motor before using the Energy-saving control.
b8-01: Energy Saving Control Selection
No.
Name
(Hex.)
b8-01
Energy Saving Control
Selection
(01CC)
0 : Disabled
1 : Enabled
2 : Automatic Optimization
Note:
Setting 2 is available only when A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM] and in Expert Mode.
b8-02: Energy Saving Gain
No.
Name
(Hex.)
b8-02
Energy Saving Gain
(01CD)
RUN
Expert
Increase the setting value to increase energy saving. If the setting value is too large, the motor will stall.
b8-03: Energy Saving Filter Time
No.
Name
(Hex.)
b8-03
Energy Saving Filter Time
(01CE)
RUN
Expert
Decrease the setting value to increase responsiveness. If the setting value is too low, operation will not be stable.
b8-04: Energy Saving Coefficient Value
No.
Name
(Hex.)
b8-04
Energy Saving Coefficient
Value
(01CF)
Expert
When you use a motor from a different manufacturer, increase the setting value in 5% increments to find the
minimum value for U1-08 [Output Power] at light loads.
When you decrease the setting value, it decreases the output voltage and decreases power consumption. If the setting
value is too low, the motor will stall.
Note:
When you do Rotational Auto-Tuning, the drive will automatically set the energy-saving coefficient.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Energy-saving control function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the gain for Energy-saving control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the responsiveness for Energy-saving control.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The default setting
is for Yaskawa motors.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.3 b: Application
Default
(Range)
0
(0 - 2)
Default
(Range)
Determined by A1-02
(0.0 - 10.0)
Default
(Range)
Determined by A1-02,C6-
01 and o2-04
(0.00 - 10.00 s)
Default
(Range)
Determined by C6-01, E2-
11, and o2-04
(0.00 - 655.00)
12
763

Advertisement

Table of Contents
loading

Table of Contents