YASKAWA GA800 Technical Reference page 647

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

No.
Name
(Hex.)
U1-10
Input Terminal Status
(0049)
U1-11
Output Terminal Status
(004A)
U1-12
Drive Status
(004B)
U1-13
Terminal A1 Level
(004E)
U1-14
Terminal A2 Level
(004F)
U1-15
Terminal A3 Level
(0050)
U1-16
SFS Output Frequency
(0053)
U1-17
DI-A3 Input Status
(0058)
U1-18
oPE Fault Parameter
(0061)
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Shows the status of the MFDI terminal where 1 = ON, 0 = OFF.
For example, U1-10 shows "00000011" when terminals S1 and S2 are ON.
bit0 : Terminal S1 (MFDI 1)
bit1 : Terminal S2 (MFDI 2)
bit2 : Terminal S3 (MFDI 3)
bit3 : Terminal S4 (MFDI 4)
bit4 : Terminal S5 (MFDI 5)
bit5 : Terminal S6 (MFDI 6)
bit6 : Terminal S7 (MFDI 7)
bit7 : Terminal S8 (MFDI 8)
V/f
CL-V/f
OLV
CLV
AOLV
Shows the status of the MFDO terminal where 1 = ON and 0 = OFF.
For example, U1-11 shows "00000011" when terminals M1 and M3 are ON.
Note:
When H2-xx = 100 to 1A7 [Inverse Output of Function], U1-11 does not show the status in
inverse.
bit0 : Terminal M1-M2
bit1 : Terminal M3-M4
bit2 : Terminal M5-M6
bit3 : Not used (normal value of 0).
bit4 : Not used (normal value of 0).
bit5 : Not used (normal value of 0).
bit6 : Not used (normal value of 0).
bit7 : Fault relay MA/MB-MC
V/f
CL-V/f
OLV
CLV
AOLV
Shows drive status where 1 = ON and 0 = OFF.
For example, U1-12 shows "00000101" during run with the Reverse Run command.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive ready
bit6 : During minor fault detection
bit7 : During fault detection
V/f
CL-V/f
OLV
CLV
AOLV
Shows the signal level of terminal A1.
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Shows the signal level of terminal A2.
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Shows the signal level of terminal A3.
Unit: 0.1%
V/f
CL-V/f
OLV
CLV
AOLV
Shows the output frequency after soft start. Shows the frequency with acceleration and deceleration
times and S-curves. Parameter o1-03 [Keypad Display Unit Selection] sets the display units.
Unit: 0.01 Hz
V/f
CL-V/f
OLV
CLV
AOLV
Shows the reference value input from DI-A3 option.
Shows the input signal for DI-A3 in hexadecimal as set in F3-01 [Digital Input Function Selection].
3FFFF: Set (1 bit) + Sign (1 bit) + 16 bit
V/f
CL-V/f
OLV
CLV
AOLV
Shows the parameter number that caused the oPE02 [Parameter Range Setting Error] or oPE08
[Parameter Selection Error].
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.17 U: Monitors
MFAO Signal Level
No signal output available
No signal output available
No signal output available
10 V = 100% (0 V to +10 V)
10 V = 100% (0 V to +10 V)
10 V = 100% (-10 V to +10
V)
10 V = Maximum frequency
(0 V to +10 V)
No signal output available
No signal output available
11
647