7.6 Parameter Setting Errors
Code
Name
oPE33
Digital Output Selection Error
406
Causes
These two parameters are set at the same time:
• H2-60 ≠ F [Term M1-M2 Secondary Function ≠
Not Used]
• H2-01 = 1xx [Term M1-M2 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-63 ≠ F [Term M3-M4 Secondary Function ≠
Not Used]
• H2-02 = 1xx [Term M3-M4 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-66 ≠ F [Term M5-M6 Secondary Function ≠
Not Used]
• H2-03 = 1xx [Term M5-M6 Function Selection =
Inverse output of xx]
These parameter pairs are set incorrectly:
• H2-21 [Comparator 1 Lower Limit] > H2-22
[Comparator 1 Upper Limit]
• H2-27 [Comparator 2 Lower Limit] > H2-28
[Comparator 2 Upper Limit]
Possible Solutions
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
It is not possible to set H2-01 to H2-03 = 1xx [Inverse output of
xx] when using output functions for logic operations (H2-60,
H2-63, H2-66 ≠ F).
• Set parameters H2-21 ≤ H2-22.
• Set parameters H2-27 ≤ H2-28.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference