YASKAWA GA800 Technical Reference page 952

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.8 H: Terminal Functions
H6-05: Terminal RP Filter Time
No.
Name
(Hex.)
H6-05
Terminal RP Filter Time
(0430)
RUN
H6-06: Terminal MP Monitor Selection
No.
Name
(Hex.)
H6-06
Terminal MP Monitor
Selection
(0431)
RUN
Note:
To use in through mode or when terminal MP is not used, set this parameter to 000 or 031.
When you use the pulse train monitor, make sure that you connect peripheral devices as specified by these load
conditions:
Incorrect connections can make the characteristics not sufficient or cause mechanical damage.
• Use the pulse train monitor as the sourcing output.
• Use the pulse train monitor as the sinking input
External Power Supply (V)
Sinking current (mA)
952
V/f
CL-V/f
OLV
Sets the time constant for the pulse train input primary delay filters.
V/f
CL-V/f
OLV
Sets a function for pulse train monitor output terminal MP. Sets the "x-xx" part of the Ux-xx monitor.
Output Voltage
VRL(V)
5 V or more
8 V or more
10 V or more
Figure 12.115 Circuit Diagram When Used as the Sourcing Output
Figure 12.116 Circuit Diagram When Used as the Sinking Input
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
(000, 031, 101, 102, 105,
116, 501, 502, 801 - 809,
821 - 825, 831 - 839, 851 -
Load Impedance (kΩ)
1.5 kΩ or more
4.0 kΩ or more
10 kΩ or more
12 VDC ± 10%, 15 VDC ± 10%
16 mA or less
Default
(Range)
0.10 s
(0.00 - 2.00 s)
Default
(Range)
102
855)

Advertisement

Table of Contents
loading

Table of Contents