YASKAWA GA800 Technical Reference page 899

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Note:
• When A1-02 = 8 [Control Method Selection = EZOLV], this function is available with a PM motor.
• Refer to
b2: DC Injection Braking and Short Circuit Braking on page 729
61: Speed Search from Fmax
Setting Value
Function
61
Speed Search from Fmax
When the terminal is activated for b3-24 = 2 [Speed Search Method Selection = Current Detection 2], the drive starts
speed search from the maximum output frequency.
Note:
• The drive will detect oPE03 [Multi-Function Input Setting Err] if you set H1-xx = 61 and 62 at the same time.
• Refer to "b3: Speed Search" for more information.
62: Speed Search from Fref
Setting Value
Function
62
Speed Search from Fref
When the terminal is activated for b3-24 = 2 [Speed Search Method Selection = Current Detection 2], the drive starts
speed search from the frequency reference.
Note:
• The drive will detect oPE03 [Multi-Function Input Setting Err] if you set H1-xx = 61 and 62 at the same time.
• Refer to "b3: Speed Search" for more information.
63: Field Weakening
Setting Value
Function
63
Field Weakening
Note:
Refer to
d6: Field Weakening /Forcing on page 814
65: KEB Ride-Thru 1 Activate (N.C.)
Setting Value
Function
65
KEB Ride-Thru 1 Activate
(N.C.)
ON : Normal operation
OFF : Deceleration during momentary power loss
When you enable KEB Ride-Thru 1, set L2-29 [KEB Method Selection]. The drive operates with the selected KEB
method.
Note:
• If you set KEB Ride-Thru 1 [H1-xx = 65, 66] and KEB Ride-Thru 2 [H1-xx = 7A, 7B] at the same time, the drive will detect oPE03 [Multi-
Function Input Setting Err].
• Refer to
KEB Ride-Thru Function on page 964
66: KEB Ride-Thru 1 Activate (N.O.)
Setting Value
Function
66
KEB Ride-Thru 1 Activate
(N.O.)
ON : Deceleration during momentary power loss
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at Start = Disabled]
to not allow speed search at start.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at Start = Disabled]
to not allow speed search at start.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01 [Field
Weakening Level] and d6-02 [Field Weakening Frequency Limit] when the input terminal is activated.
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.C.).
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets operation of the KEB1 function through the KEB Ride-Thru 1 (N.O.).
for more information.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 H: Terminal Functions