12.6 E: Motor Parameters
E9-10: Motor Line-to-Line Resistance
No.
Name
(Hex.)
E9-10
Motor Line-to-Line
Resistance
(11ED)
Note:
This value is the motor line-to-line resistance. Do not set this parameter with the resistance per phase.
Stationary Auto-Tuning automatically sets this parameter. If you cannot do Stationary Auto-Tuning, use the test report
from the motor manufacturer. Use one of these formulas to calculate the motor line-to-line resistance:
• E-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.822
• B-type insulation: [the resistance value (Ω) shown on the test report at 75 °C] × 0.822
• F-type insulation: [the resistance value (Ω) shown on the test report at 115 °C] × 0.728
838
V/f
CL-V/f
OLV
CLV
AOLV
Sets the line-to-line resistance for the motor stator windings.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
Determined by o2-04
(0.000 - 65.000 Ω)