Drive Watt Loss; Class - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

10.7 Drive Watt Loss

10.7
Drive Watt Loss
200 V Class
Rated Output Current
Model
2004
2006
2008
2010
2012
2018
2021
2030
2042
2056
2070
2082
2110
2138
2169
2211
2257
2313
2360
2415
Rated Output Current
Model
2004
2006
2008
2010
2012
2018
2021
2030
2042
2056
2070
2082
2110
2138
2169
496
Table 10.15 Drive Watt Loss (Heavy Duty)
Carrier Frequency
A
kHz
3.5
8
5
8
6.9
8
8
8
11
8
14
8
17.5
8
25
8
33
8
47
8
60
8
75
8
88
8
115
8
145
5
180
5
215
5
283
5
346
5
415
5
Table 10.16 Drive Watt Loss (Normal Duty)
Carrier Frequency
A
kHz
4.2
2
6
2
8
2
9.6
2
12.2
2
17.5
2
21
2
30
2
42
2
56
2
70
2
82
2
110
2
138
2
169
2
Interior Unit Loss
Cooling Fin Loss
W
35
37
40
44
50
47
56
74
88
112
145
179
155
212
275
314
398
1252
502
1643
582
1978
644
2359
Interior Unit Loss
Cooling Fin Loss
W
35
38
42
49
56
53
75
95
129
149
177
202
192
269
338
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Total Loss
W
W
19
54
26
63
36
76
43
87
61
111
82
129
105
161
174
248
183
271
267
379
373
518
478
657
563
718
680
892
820
1095
991
1305
1650
2145
2560
3003
Total Loss
W
W
18
53
25
63
34
76
46
95
62
118
88
141
125
200
206
301
227
356
302
451
403
580
467
669
631
823
814
1083
941
1279

Advertisement

Table of Contents
loading