10.6 Drive Specifications
Item
200 V Class: Stops when the DC bus voltage is more than approximately 410 V
Overvoltage
Protection
400 V Class: Stops when the DC bus voltage is more than approximately 820 V
200 V Class: Stops when the DC bus voltage decreases to less than approximately 190 V
Undervoltage
Protection
400 V Class: Stops when the DC bus voltage decreases to less than approximately 380 V
Stops when power loss is longer than 15 ms.
Continues operation if power loss is shorter than 2 s (depending on parameter settings).
Momentary Power
Note:
Loss Ride-thru
• Stop time may be shortened depending on the load and motor speed.
• Drive capacity will change the continuous operation time. A Momentary Power Loss Recovery Unit is necessary to continue operation through a 2 s
power loss on models 2004 to 2056 and 4002 to 4031.
Heatsink Overheat
The drive stops when the thermistor detects an IGBT temperature more than approximately 100 °C (212 °F). The trip temperature level is different for different
Protection
drive models.
Braking Resistor
Overheat detection for braking resistor (optional ERF-type, 3% ED)
Overheat Protection
Stall prevention is available during acceleration, deceleration, and during run.
Stall Prevention
Electronic circuit protection
Note:
Ground Fault
This protection detects ground faults during run. The drive will not provide protection when:
Protection
• There is a low-resistance ground fault for the motor cable or terminal block
• Energizing the drive when there is a ground fault.
DC Bus Charge LED Charge LED illuminates when DC bus voltage is more than 50 V.
Models 2004 to 2138 and 4002 to 4168 have a braking transistor.
Braking Transistor
Models 2110 to 2415 and 4060 to 4720 have a DC link choke.
DC Link Choke
Item
Indoors
Area of Use
Overvoltage Category III
Permitted frequency fluctuation: ±5%
Permitted voltage fluctuation: -15% to +10%
200 V Class:
• Three-phase AC power supply 200 V to 240 V at 50/60 Hz 
Power Supply
• DC power supply 270 V to 340 V
400 V Class:
• Three-phase AC power supply 380 V to 480 V at 50/60 Hz
• DC power supply 513 V to 679 V
6-Phase/12-Pulse 400 V Class:
• Three-phase AC power supply 380 V to 480 V at 50/60 Hz
IP00/UL Open Type: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Open Type/Heatsink External Mounting: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1: -10 °C to +40 °C (14 °F to 104 °F)
IP55/UL Type 12 Heatsink External Mounting; front side: -10 °C to +50 °C (14 °F to 122 °F)
Ambient Temperature
IP55/UL Type 12 Heatsink External Mounting; back side: -10 °C to +40 °C (14 °F to 104 °F)
Setting
• When you install the drive in an enclosure, use a cooling fan or air conditioner to keep the internal air temperature in the permitted range.
• Do not let the drive freeze.
• You can use IP00/IP20/UL Open Type drives at a maximum of 60 °C (140 °F) when you derate the output current.
• You can use IP20/UL Type 1 drives at a maximum of 50 °C (122 °F) when you derate the output current.
95% RH or less
Humidity
Do not let condensation form on the drive.
Storage Temperature -20 °C to +70 °C (-4 °F to +158 °F) (short-term temperature during transportation)
Pollution degree 2 or less
Install the drive in an area without:
• Oil mist, corrosive or flammable gas, or dust
• Metal powder, oil, water, or other unwanted materials
Surrounding Area
• Radioactive materials or flammable materials, including wood
• Harmful gas or fluids
• Salt
• Direct sunlight
494
Specification
Table 10.13 Environment
Specification
YASKAWA SIEPC71061737D GA800 Drive Technical Reference