12.4 C: Tuning
Figure 12.58 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
• When C6-05 ≤ 7, the drive disables C6-04. The carrier frequency is fixed to the value set to C6-03.
• The drive detects oPE11 [Carrier Frequency Setting Error] when these conditions are correct at the same time:
–C6-05 ≥ 6
–C6-04 ≥ C6-03
• When A1-02 = 0, 2, 5, 8 [Control Method Selection = v/f, OLV, OLV/PM, EZOLV], in the area where the output frequency is more than C6-
03 and C6-12, the carrier frequency = output frequency × 12, and it will change with the output frequency.
C6-04: Carrier Frequency Lower Limit
No.
Name
(Hex.)
C6-04
Carrier Frequency Lower
Limit
(0226)
Set C6-03 [Carrier Frequency Upper Limit], C6-04, and C6-05 [Carrier Freq Proportional Gain] to make the carrier
frequency change linearly with the output frequency.
Note:
The drive detects oPE11 [Carrier Frequency Setting Error] when these conditions are correct at the same time:
• C6-04 ≥ C6-03
• C6-05 ≥ 6
C6-05: Carrier Freq Proportional Gain
No.
Name
(Hex.)
C6-05
Carrier Freq Proportional
Gain
(0227)
Set C6-03 [Carrier Frequency Upper Limit], C6-04 [Carrier Frequency Lower Limit], and C6-05 to make the carrier
frequency change linearly with the output frequency.
C6-09: Carrier Freq at Rotational Tune
No.
Name
(Hex.)
C6-09
Carrier Freq at Rotational
Tune
(022B)
794
Figure 12.59 Carrier Frequency when C6-03 = 2.0 kHz, E1-04 = 400.0 Hz
V/f
CL-V/f
OLV
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
V/f
CL-V/f
OLV
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency Selection =
User Defined (C6-03 to C6-05)] to set this parameter.
V/f
CL-V/f
OLV
Sets the Auto-Tuning carrier frequency. Usually it is not necessary to change this setting.
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
CLV
AOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
Determined by C6-02
(1.0 - 15.0 kHz)
Default
(Range)
Determined by C6-02
(0 - 99)
Default
(Range)
0
(0, 1)