The value set in b2-04 and the output frequency when the drive receives the Stop command determine the DC
Injection Braking time. The drive calculates the DC Injection Braking time as in
Note:
If the drive detects oC [Overcurrent] when it uses DC Injection Braking to stop the motor, set L2-03 to a high value that will not trigger oC.
3 : Coast to Stop with Timer
When you enter the Stop command or turn OFF the Run command, the drive turns OFF the output and coasts the
motor to stop. The drive ignores the Run command until the "Run wait time t" is expired.
To start the drive again, wait until the the "Run wait time t" is expired then enter the Run command.
The active deceleration time and the output frequency when drive receives the Stop command determine the length of
"Run wait time t".
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Figure 12.14 DC Injection Braking to Stop
Figure 12.15 DC Injection Braking Time and Output Frequency
Figure 12.16 Coast to Stop with Timer
12.3 b: Application
Figure
12.15.
12
721