• 00ACH (U1-05: Motor Speed)
• 00ADH (U1-05: Motor Speed)
H5-20: Communication Parameters Reload
No.
Name
(Hex.)
H5-20
Communication Parameters
Reload
(0B57)
0 : Reload at Next Power Cycle
1 : Reload Now
Note:
• The setting value automatically returns to H5-20 = 0 after you enable MEMOBUS/Modbus communications parameter changes.
• The setting values of these parameters are enabled:
–H5-01 [Drive Node Address]
–H5-02 [Communication Speed Selection]
–H5-03 [Communication Parity Selection]
–H5-06 [Drive Transmit Wait Time]
H5-22: Speed Search from MODBUS
No.
Name
(Hex.)
H5-22
Speed Search from
MODBUS
(11CF)
0 : Disabled
1 : Enabled
If you set H5-22 = 1 and H1-xx = 62 [Speed Search from Fref] at the same time, the drive will detect oPE03 [Multi-
Function Input Setting Err].
H5-25: Function 5A Register 1 Selection
No.
Name
(Hex.)
H5-25
Function 5A Register 1
Selection
(1589)
RUN
H5-26: Function 5A Register 2 Selection
No.
Name
(Hex.)
H5-26
Function 5A Register 2
Selection
(158A)
RUN
H5-27: Function 5A Register 3 Selection
No.
Name
(Hex.)
H5-27
Function 5A Register 3
Selection
(158B)
RUN
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to immediately enable updated MEMOBUS/Modbus communications parameters.
V/f
CL-V/f
OLV
CLV
AOLV
Enables the MEMOBUS/Modbus communication register Speed Search function (bit0 of 15DFH).
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
V/f
CL-V/f
OLV
CLV
AOLV
Returns the contents of the specified MEMOBUS/Modbus communications register when responding
to the master device.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 H: Terminal Functions
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0044H (U1-05)
(0000H - FFFFH)
Default
(Range)
0045H (U1-06)
(0000H - FFFFH)
Default
(Range)
0042H (U1-03)
(0000H - FFFFH)
12