YASKAWA GA800 Technical Reference page 1046

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.11 o: Keypad-Related Settings
o2-07: Keypad RUN Direction @ Power-up
No.
Name
(Hex.)
o2-07
Keypad RUN Direction @
Power-up
(0527)
This parameter is enabled in these conditions:
• When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
• In LOCAL Mode
0 : Forward
1 : Reverse
o2-09: Reserved
No.
Name
(Hex.)
o2-09
Reserved
(050D)
o2-23: External 24V Powerloss Detection
No.
Name
(Hex.)
o2-23
External 24V Powerloss
Detection
(11F8)
RUN
Note:
The drive will not run when it is operating from one 24-V external power supply.
0 : Disabled
The drive does not detect the loss of the 24-V external power supply.
1 : Enabled
The keypad shows the L24v [Loss of External Power 24 Supply] indicator if the drive detects the loss of the 24-V
external power supply.
Note:
A minor fault signal is not output from H2-xx = 10 [MFDO Function Selection = Alarm].
o2-24: LED Light Function Selection
No.
Name
(Hex.)
o2-24
LED Light Function
Selection
(11FE)
Note:
When you initialize the drive with parameter A1-03 [Initialize Parameters], the drive will not reset this parameter.
0 : Enable Status Ring & Keypad LED
1 : LED Status Ring Disable
2 : Keypad LED Light Disable
o2-26: Alarm Display at Ext. 24V Power
No.
Name
(Hex.)
o2-26
Alarm Display at Ext. 24V
Power
(1563)
1046
V/f
CL-V/f
OLV
CLV
AOLV
Sets the direction of motor rotation when the drive is energized and the keypad is the Run command
source.
-
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to give a warning if the backup external 24 V power supply turns off when the main
circuit power supply is in operation.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to show the LED status rings and keypad LED lamps.
V/f
CL-V/f
OLV
CLV
AOLV
When you connect a backup external 24 V power supply, this parameter sets the function to trigger
an alarm when the main circuit power supply voltage decreases.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
0
(0, 1)
Default
(Range)
-
Default
(Setting Range)
0
(0, 1)
Default
(Setting Range)
2
(0 - 2)
Default
(Range)
1
(0, 1)

Advertisement

Table of Contents
loading

Table of Contents