No.
Name
(Hex.)
F6-61
DeviceNet Time Scaling
(03DC)
F6-62
DeviceNet Heartbeat
Interval
(03DD)
F6-63
DeviceNet Network
MAC ID
(03DE)
F6-64
Dynamic Out Assembly
109 Param1
(03DF)
F6-65
Dynamic Out Assembly
109 Param2
(03E0)
F6-66
Dynamic Out Assembly
109 Param3
(03E1)
F6-67
Dynamic Out Assembly
109 Param4
(03E2)
F6-68
Dynamic In Assembly
159 Param 1
(03E3)
F6-69
Dynamic In Assembly
159 Param 2
(03E4)
F6-70
Dynamic In Assembly
159 Param 3
(03C7)
F6-71
Dynamic In Assembly
159 Param 4
(03C8)
F6-72
PowerLink Node Address
(081B)

F7: Communication Options

No.
Name
(Hex.)
F7-01
IP Address 1
(03E5)
F7-02
IP Address 2
(03E6)
F7-03
IP Address 3
(03E7)
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the time scale of the DeviceNet communication master.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the heartbeat for DeviceNet communication. Set this parameter to 0 to disable the
heartbeat function.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function to see the actual DeviceNet MAC address using the keypad. This
parameter functions as a monitor only.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Configurable Output 1 written to the MEMOBUS register.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Configurable Output 2 written to the MEMOBUS register.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Configurable Output 3 written to the MEMOBUS register.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Configurable Output 4 written to the MEMOBUS register.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Configurable Input 1 read from the MEMOBUS register.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Configurable Input 2 read from the MEMOBUS register.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Configurable Input 3 read from the MEMOBUS register.
V/f
CL-V/f
OLV
CLV
AOLV
Sets Configurable Input 4 read from the MEMOBUS register.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the node ID for PowerLink communication.
Note:
Be sure to set an address that is different than all other node addresses. Do not set this
parameter to 0.
Description
V/f
CL-V/f
OLV
CLV
AOLV
Sets the first octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 1 to 4] to set the IP Address. Be sure to
set a different IP address for each drive on the network.
• Also set parameters F7-05 to F7-12 [Subnet Mask 1 to 4, Gateway Address 1 to 4].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the second octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 1 to 4] to set the IP Address. Be sure to
set a different IP address for each drive on the network.
• Also set parameters F7-05 to F7-12 [Subnet Mask 1 to 4, Gateway Address 1 to 4].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the third octet of the IP Address for the device that is connecting to the network.
Restart the drive after you change this parameter.
Note:
When F7-13 = 0 [Address Mode at Startup = Static]:
• Use parameters F7-01 to F7-04 [IP Address 1 to 4] to set the IP Address. Be sure to
set a different IP address for each drive on the network.
• Also set parameters F7-05 to F7-12 [Subnet Mask 1 to 4, Gateway Address 1 to 4].
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
11.9 F: Options
Default
Ref.
(Range)
0
873
(-15 - +15)
0
873
(0 - 10)
63
873
(0 - 63)
0000H
873
(0000H - FFFFH)
0000H
873
(0000H - FFFFH)
0000H
873
(0000H - FFFFH)
0000H
873
(0000H - FFFFH)
0000H
873
(0000H - FFFFH)
0000H
873
(0000H - FFFFH)
0000H
873
(0000H - FFFFH)
0000H
873
(0000H - FFFFH)
0
874
(0 - 255)
Default
Ref.
(Range)
192
874
(0 - 255)
168
874
(0 - 255)
1
874
(0 - 255)
579