Wire Gauge and Torque Specifications for UL Listing
WARNING! Electrical Shock Hazard.
Make sure that the protective ground wire complies with technical standards and local safety regulations. The IEC/EN 61800-5-
1:2007 standard specifies that you must wire the power supply to automatically de-energize when the protective ground wire
disconnects. You can also connect a protective ground wire that has a minimum cross-sectional area of 10mm
mm
2
(aluminum wire). The leakage current of the drive will be more than 3.5 mA in drive models;
• 2xxxB
• 2xxxC
• 4002B to 4371B
• 4002C to 4371C (with built-in EMC filter turned ON)
• 4414 to 4720
• T414 to T720
If you do not obey the standards and regulations, it can cause serious injury or death.
Refer to
Three-Phase 200 V Class on page
Class on page 95
for the recommended wire gauges and tightening torques of the main circuit terminals.
Note:
• The recommended wire gauges are based on drive continuous current ratings with 75 °C (167 °F) 600 V class 2 heat-resistant indoor PVC
wire. Assume these conditions:
–Ambient temperature: 40 °C (104 °F) maximum
–Wiring distance: 100 m (328 ft) maximum
–Normal Duty rated current value
• Use terminals +1, +2, +3, -, B1, and B2 to connect a peripheral option such as a DC link choke or a braking resistor. Do not connect other
items to these terminals.
• Refer to the instruction manual for each device for recommended wire gauges to connect peripheral devices or options to terminals +1, +2,
+3, -, B1, and B2. Contact Yaskawa or your nearest sales representative if the recommended wire gauges for the peripheral devices or
options are out of the range of the applicable gauges for the drive.
• The metric wire gauge values are provided as reference information from equivalent AWG sizes and not exactly the same sizes as the
AWG/kcmil values. Obey local safety regulations for wire sizes and make sure that the ferrule or crimp terminals are correct for your size.
Three-Phase 200 V Class
Model
Terminal
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2004
-, +1, +2
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
2006
-, +1, +2
B1, B2
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
85,
Three-Phase 400 V Class on page
Applicable Gauge
Recomm. Gauge
AWG, kcmil
AWG, kcmil
(mm
2
)
14 - 6
14
(2.5 - 16)
14 - 6
14
(2.5 - 16)
14 - 3
14
(2.5 - 25)
14 - 10
14
(2.5 - 6.0)
14 - 8
10
(2.5 - 10)
14 - 6
14
(2.5 - 16)
14 - 6
14
(2.5 - 16)
14 - 3
14
(2.5 - 25)
14 - 10
14
(2.5 - 6.0)
14 - 8
10
(2.5 - 10)
90, and
6-Phase/12-Pulse 400 V
IP20 Applicable
Wire Stripping
*1
Gauge
*2
Length
AWG, kcmil
mm
(mm
2
)
14 - 6
10
(2.5 - 16)
14 - 6
10
(2.5 - 16)
14 - 3
18
(2.5 - 25)
14 - 10
10
(2.5 - 6.0)
-
-
14 - 6
10
(2.5 - 16)
14 - 6
10
(2.5 - 16)
14 - 3
18
(2.5 - 25)
14 - 10
10
(2.5 - 6.0)
-
-
3.3 Main Circuit Wiring
2
(copper wire) or 16
Tightening
Terminal Screw
Torque
Size and Shape
N∙m (lbf∙in)
1.5 - 1.7
M4
(13.5 - 15)
1.5 - 1.7
M4
(13.5 - 15)
2.3 - 2.5
M5
*3
(19.8 - 22)
1.5 - 1.7
M4
(13.5 - 15)
1.2 - 1.5
M4
(10.6 - 13.3)
1.5 - 1.7
M4
(13.5 - 15)
1.5 - 1.7
M4
(13.5 - 15)
2.3 - 2.5
M5
*3
(19.8 - 22)
1.5 - 1.7
M4
(13.5 - 15)
1.2 - 1.5
M4
(10.6 - 13.3)
85