YASKAWA GA800 Technical Reference page 799

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

d1-02: Reference 2
No.
Name
(Hex.)
d1-02
Reference 2
(0281)
RUN
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03 = 1 [0.01% (100% = E1-04)].
• To set d1-02 to Multi-Step Speed 2, set H3-02, H3-06, and H3-10 ≠ 2 [MFAI Function Select ≠ Auxiliary Frequency Reference 1]. When
the status is the default setting, set H3-06 = F [Terminal A3 Function Selection = Not Used].
d1-03: Reference 3
No.
Name
(Hex.)
d1-03
Reference 3
(0282)
RUN
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03 = 1 [0.01% (100% = E1-04)].
• To set d1-03 to Multi-Step Speed 3, set H3-02, H3-06, and H3-10 ≠ 3 [MFAI Function Select ≠ Auxiliary Frequency Reference 2].
d1-04: Reference 4
No.
Name
(Hex.)
d1-04
Reference 4
(0283)
RUN
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03 = 1 [0.01% (100% = E1-04)].
• This parameter sets the frequency reference of Multi-Step Speed 4.
d1-05: Reference 5
No.
Name
(Hex.)
d1-05
Reference 5
(0284)
RUN
Note:
• The upper limit value changes when the E1-04 [Maximum Output Frequency] and d2-01 [Frequency Reference Upper Limit] values
change.
• When A1-02 = 6, 7 [Control Method Selection = AOLV/PM, CLV/PM], the drive changes o1-03 = 1 [0.01% (100% = E1-04)].
• This parameter sets the frequency reference of Multi-Step Speed 5.
d1-06: Reference 6
No.
Name
(Hex.)
d1-06
Reference 6
(0285)
RUN
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the frequency reference in the units from o1-03 [Frequency Display Unit Selection].
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.5 d: References
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
Default
(Range)
0.00 Hz
(0.00 - 590.00 Hz)
12