YASKAWA GA800 Technical Reference page 1037

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Note:
• Select the setting unit of these parameters:
–d1-01 to d1-17 [Reference 1 to 16, Jog Reference]
–U1-01 [Frequency Reference]
–U1-02 [Output Frequency]
–U1-05 [Motor Speed]
–U1-16 [SFS Output Frequency]
–U4-14 [PeakHold Output Freq]
–U6-27 [FeedFwd Estimate Spd]
• For monitor 2, the setting value is always 0 [Hz Unit].
0 : 0.01 Hz
1 : 0.01% (100% = E1-04)
The maximum output frequency is 100%.
2 : min
-1
(r/min) units
The drive uses the maximum output frequency and number of motor poles to calculate this value automatically.
Note:
When you set o1-03 = 2, make sure that you set the number of motor poles in these parameters:
• E2-04 [Motor Pole Count]
• E4-04 [Motor 2 Motor Poles]
• E5-04 [PM Motor Pole Count]
• E9-08 [Motor Pole Count]
3 : User Units (o1-10 & o1-11)
Uses o1-10 [User Units Maximum Value] and o1-11 [User Units Decimal Position] to set the unit of measure. The
value of parameter o1-10 is the value when you remove the decimal point from the maximum output frequency.
Parameter o1-11 is to the number of digits after the decimal point in the maximum output frequency.
To display a maximum output frequency of 100.00, set parameters to these values:
• o1-10 = 10000
• o1-11 = 2 [Two Decimal Places (XXX.XX)]
o1-04: V/f Pattern Display Unit
No.
Name
(Hex.)
o1-04
V/f Pattern Display Unit
(0503)
Note:
• Select the setting unit of these parameters:
–E1-04 [Maximum Output Frequency]
–E1-06 [Base Frequency]
–E1-07 [Mid Point A Frequency]
–E1-09 [Minimum Output Frequency]
–E1-11 [Mid Point B Frequency]
–E9-02 [Maximum Speed]
–E9-04 [Base Frequency]
• For monitor 2, the setting value is always 0 [Hz Unit].
0 : Hz
1 : min
-1
(r/min) units
When you set o1-04 = 1, make sure that you set the number of motor poles in these parameters:
• E2-04 [Motor Pole Count]
• E5-04 [PM Motor Pole Count]
• E9-08 [Motor Pole Count]
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the setting unit for parameters that set the V/f pattern frequency.
12.11 o: Keypad-Related Settings
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Default
(Range)
Determined by A1-02
(0, 1)
12
1037