• When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will reset the manually set values for
E3-04 to E3-13 [Motor 2 Base Voltage] to default values.
E3-01: Motor 2 Control Mode Selection
No.
Name
(Hex.)
E3-01
Motor 2 Control Mode
Selection
(0319)
Note:
• When you change this setting, the drive will set all parameters that are dependent on this parameter to their default settings.
• Parameter L1-01 [Motor Overload (oL1) Protection] sets the protection operation of oL1 [Motor Overload] the same as Motor 1.
• When you use parameter A1-03 [Initialize Parameters] to initialize the drive, this parameter is not reset.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
E3-04: Motor 2 Maximum Output Frequency
No.
Name
(Hex.)
E3-04
Motor 2 Maximum Output
Frequency
(031A)
E3-05: Motor 2 Maximum Output Voltage
No.
Name
(Hex.)
E3-05
Motor 2 Maximum Output
Voltage
(031B)
E3-06: Motor 2 Base Frequency
No.
Name
(Hex.)
E3-06
Motor 2 Base Frequency
(031C)
E3-07: Motor 2 Mid Point A Frequency
No.
Name
(Hex.)
E3-07
Motor 2 Mid Point A
Frequency
(031D)
E3-08: Motor 2 Mid Point A Voltage
No.
Name
(Hex.)
E3-08
Motor 2 Mid Point A Voltage
(031E)
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the control method for motor 2.
V/f
CL-V/f
OLV
CLV
AOLV
Set the maximum output frequency for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the maximum output voltage for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the base frequency for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output frequency for the motor 2 V/f pattern.
V/f
CL-V/f
OLV
CLV
AOLV
Sets a middle output voltage for the motor 2 V/f pattern.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.6 E: Motor Parameters
Default
(Range)
0
(0 - 3)
Default
(Range)
Determined by E3-01
(40.0 - 590.0 Hz)
Default
(Range)
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)
Default
(Range)
Determined by E3-01
(0.0 - E3-04)
Default
(Range)
Determined by E3-01
(0.0 - E3-04)
Default
(Range)
Determined by E3-01
(200 V Class: 0.0 - 255.0 V,
400 V Class: 0.0 - 510.0 V)