YASKAWA GA800 Technical Reference page 1045

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

Drive Model
4103
4140
4168
4208
4250
4302
Drive Model
T103
T140
T168
T208
T250
T302
o2-05: Home Mode Freq Ref Entry Mode
No.
Name
(Hex.)
o2-05
Home Mode Freq Ref Entry
Mode
(0509)
0 : ENTER Key Required
You must push
to use the keypad to change the frequency reference value.
1 : Immediate / MOP-style
The frequency reference changes when you enter it with the keypad. This then changes the output frequency. It is not
necessary to push
. The drive keeps the frequency reference for 5 seconds after you use
keypad to change the frequency reference value.
o2-06: Keypad Disconnect Detection
No.
Name
(Hex.)
o2-06
Keypad Disconnect
Detection
(050A)
This parameter continues to operate if the keypad installed to the drive becomes disconnected.
This parameter is enabled in these conditions:
• When b1-02 = 0 [Run Command Selection 1 = Keypad] or b1-16 = 0 [Run Command Selection 2 = Keypad]
• In LOCAL Mode
0 : Disabled
The drive continues operation when it detects a keypad disconnection.
1 : Enabled
The drive stops operation, detects oPr [Keypad Connection Fault], and the motor coasts to stop when the drive
detects a keypad disconnection.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
o2-04 Setting
00A3
00A4
00A5
00A6
00A7
00A8
Table 12.76 6-Phase/12-Pulse 400 V Class
o2-04 Setting
01A3
01A4
01A5
01A6
01A7
01A8
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that makes it necessary to push
reference value while in Drive Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the function that stops the drive if you disconnect the keypad connection cable from the drive or
if you damage the cable while the keypad is the Run command source.
12.11 o: Keypad-Related Settings
Drive Model
4371
4414
4477
4568
4605
4720
Drive Model
T371
T414
T477
T568
T605
T720
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
to use the keypad to change the frequency
Description
OLV/PM
OLV/PM AOLV/PM CLV/PM EZOLV
o2-04 Setting
00A9
00AA
00AC
00AD
00AE
00AF
o2-04 Setting
01A9
01AA
01AC
01AD
01AE
01AF
Default
(Setting Range)
0
(0, 1)
and
on the
Default
(Range)
1
(0, 1)
12
1045

Advertisement

Table of Contents
loading

Table of Contents