b5-67: PID Differential FB Monitor Lvl
No.
Name
(Hex.)
b5-67
PID Differential FB Monitor
Lvl
(11DF)
0 : Absolute
1 : Bi-directional (+/-)
b5-89: Sleep Method Selection
No.
Name
(Hex.)
b5-89
Sleep Method Selection
(0B89)
RUN
0 : Standard
1 : EZ Sleep/Wake-up
b5-90: EZ Sleep Unit
No.
Name
(Hex.)
b5-90
EZ Sleep Unit
(0B90)
0 : 0.1Hz units
1 : rev/min
b5-91: EZ Sleep Minimum Speed
No.
Name
(Hex.)
b5-91
EZ Sleep Minimum Speed
(0B91)
RUN
Note:
The value of b5-90 [EZ Sleep Unit] sets the units. When b5-90 changes, this parameter does not automatically update. Set this parameter
again after you change b5-90 is changed.
b5-92: EZ Sleep Level
No.
Name
(Hex.)
b5-92
EZ Sleep Level
(0B92)
RUN
Note:
When b5-90 [EZ Sleep Unit] changes, this parameter does not automatically update. Set this parameter again after you change b5-90.
b5-93: EZ Sleep Time
No.
Name
(Hex.)
b5-93
EZ Sleep Time
(0B93)
RUN
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
Sets the signal level for the monitor specified in b5-63 [PID Differential FB Monitor Sel].
V/f
CL-V/f
OLV
CLV
AOLV
Sets sleep and wake up operation when using PID.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the measurement units for b5-91 [EZ Sleep Minimum Speed] and b5-92 [EZ Sleep Level].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the largest value
from b5-91, b5-34 [PID Output Lower Limit Level], and d2-02 [Frequency Reference Lower Limit].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the value that the output frequency or motor speed must be less than for longer than b5-93 [EZ
Sleep Time] to enter Sleep Mode.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the length of time that the output frequency or motor speed must be less than b5-92 [EZ Sleep
Level] to enter Sleep Mode.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.3 b: Application
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)
Default
(Range)
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
-1
35400 min
(r/min))
Default
(Range)
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
Default
(Range)
5.0 s
(0.0 - 1000.0 s)