YASKAWA GA800 Technical Reference page 919

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

11: Fault Reset Command Active
Setting Value
Function
11
Fault Reset Command
Active
12: Timer Output
Setting Value
Function
12
Timer Output
Note:
Refer to
Timer Function Operation on page 742
13: Speed Agree 2
Setting Value
Function
13
Speed Agree 2
Note:
• The detection function operates in the two motor rotation directions.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency is in the range of "frequency reference ± L4-04".
OFF : The output frequency is not in the range of "frequency reference ± L4-04".
14: User-Set Speed Agree 2
Setting Value
Function
14
User-Set Speed Agree 2
Note:
• The detection level set in L4-03 is a signed value. The drive will only detect in one direction.
• The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM].
ON : The output frequency is in the range of "L4-03 ± L4-04" and the range of frequency reference ±
L4-04.
OFF : The output frequency is not in the range of "L4-03 ± L4-04" or the range of frequency
reference ± L4-04.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive receives the Reset command from the control circuit terminal, serial communications, or the
communication option.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the terminal as the timer output. Use this setting with the timer input set in H1-xx = 18 [MFDI Function Selection = Timer
Function].
for more information.
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of the frequency reference ± L4-04 [Speed Agree Detection Width
(+/-)].
Figure 12.95 Speed Agree 2 Time Chart
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the output frequency is in the range of L4-03 [Speed Agree Detection Level (+/-)] ± L4-04 [Speed
Agree Detection Width (+/-)] and in the range of the frequency reference ± L4-04.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
12.8 H: Terminal Functions
12
919

Advertisement

Table of Contents
loading

Table of Contents