YASKAWA GA800 Technical Reference page 746

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.3 b: Application
• Use Single Feedback Signal
Use
Table 12.26
to select how the feedback signal is input to the drive for PID control.
PID Feedback Input Method
MFAI terminal A1
MFAI terminal A2
MFAI terminal A3
Pulse train input terminal RP
• Use Two Feedback Signals and Calculate the Deviation from the Difference between Those Signals
Use
Table 12.27
to select how the second feedback value is input to the drive. The drive calculates the deviation of
the second feedback value. Set H3-02, H3-06, or H3-10 = 16 [Terminal A1/A3/A2 Function Selection = Differential
PID Feedback] to enable the second feedback signal used to calculated the deviation.
PID Differential Feedback Input Method
MFAI terminal A1
MFAI terminal A2
MFAI terminal A3
Note:
If you set two or more of H3-02, H3-06, and H3-10 to 16, it will trigger oPE07 [Analog Input Selection Error].
PID Control Block Diagram
746
Table 12.26 PID Feedback Input Method
Table 12.27 PID Differential Feedback Input Method
Figure 12.35 PID Control Block Diagram
Setting Value
Set H3-02 = B [PID Feedback].
Set H3-10 = B.
Set H3-06 = B.
Set H6-01 = 1 [PID Feedback Value].
Setting Value
Set H3-02 = 16 [Differential PID Feedback].
Set H3-10 = 16.
Set H3-06 = 16.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference