12.6 E: Motor Parameters
Note:
When you manually set V/f patterns, note these items:
• To set linear V/f characteristics at frequencies lower than E1-06 [Base Frequency], set E1-07 = E1-09 [Mid Point A Frequency = Minimum
Output Frequency]. In this application, the drive ignores E1-08 [Mid Point A Voltage].
• Set the five frequencies as specified by these rules: Incorrect settings will cause oPE10 [V/f Data Setting Error].
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04 [Minimum Output Frequency ≤ Mid Point A Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
• Setting E1-11 = 0 [Mid Point B Frequency = 0 Hz] disables E1-12 [Mid Point B Voltage]. Ensure that the four frequencies are set
according to the following rules;
E1-09 ≤ E1-07 < E1-06 ≤ E1-04
• When you use A1-03 [Initialize Parameters] to initialize the drive, it will not reset E1-03.
E1-01: Input AC Supply Voltage
No.
Name
(Hex.)
E1-01
Input AC Supply Voltage
(0300)
NOTICE: Damage to Equipment. Set E1-01 [Input AC Supply Voltage] to align with the drive input voltage (not motor voltage). If this
parameter is incorrect, the protective functions of the drive will not operate correctly and it can cause damage to the drive.
Values Related to the Drive Input Voltage
The value set in E1-01 is the base value that the drive uses for the motor protective functions in
400 V class drive, the detection level changes for some motor protective functions.
Voltage
E1-01 Setting
200 V Class
All settings
Setting value ≥ 400 V
400 V Class
Setting value < 400 V
*1
This is the protection function enabled in drives with built-in braking transistors. These values show the level that will trigger the built-in
braking transistor. Refer to "YASKAWA AC Drive Series Option Braking Unit and Braking Resistor Unit Installation Manual
(TOBPC72060001)" for more information.
*2
The value is different for different drive software versions.
• PRG: 09013 and earlier: 460 V
• PRG: 09014 and later: 500 V
818
Figure 12.72 V/f Pattern
V/f
CL-V/f
OLV
CLV
AOLV
Sets the drive input voltage.
Table 12.42 Values Related to the Drive Input Voltage
BTR Operation Level
ov Detection Level
(rr Detection Level)
410 V
394 V
820 V
788 V
820 V
788 V
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Approximate Values
L2-05
[Undervoltage
*1
Detection Lvl (Uv1)]
190 V
380 V
350 V
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
200 V Class: 240 V,
400 V Class: 480 V
(200 V Class: 155 to 255 V,
400 V Class: 310 to 510 V)
Table
12.42. With a
L2-11
L3-17
[KEB DC Bus
[DC Bus Regulation
Voltage Setpoint]
Level]
260 V
375 V
500 V
750 V
*2
500 V
750 V