H3: Analog Inputs - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

6A: Data Logger Error
Setting Value
Function
6A
Data Logger Error
90 to 93: DWEZ Digital Outputs 1 to 4
Setting Value
Function
90 to 93
DWEZ Digital Outputs 1 to
4
A0 to A7: DWEZ Extended Digital Outputs 1 to 8
Setting Value
Function
A0 to A7
DWEZ Extended Digital
Outputs 1 to 8
100 to 1A7: Inverse Outputs of 0 to A7
Setting Value
Function
100 to 1A7
Inverse Outputs of 0 to A7
For example, set H2-xx = 10E for the inverse output of E [Fault].

H3: Analog Inputs

WARNING! Sudden Movement Hazard. Do test runs and examine the drive to make sure that the command references are correct.
If you set the command reference incorrectly, it can cause damage to the drive or serious injury or death.
Drives have three analog input terminals, terminals A1, A2, and A3. H3 parameters select the functions set to these
analog input terminals and adjust signal levels.
Table 12.64
shows the functions that you can set to analog input terminals. Use H3-02, H3-06, and H3-10 [MFAI
Function Selection] to set functions.
Setting
Function
Value
0
Frequency Reference
1
Frequency Gain
2
Auxiliary Frequency Reference 1
3
Auxiliary Frequency Reference 2
4
Output Voltage Bias
5
Accel/Decel Time Gain
6
DC Injection Braking Current
7
Torque Detection Level
8
Stall Prevent Level During Run
9
Output Frequency Lower Limit
B
PID Feedback
C
PID Setpoint
D
Frequency Bias
Note:
All analog input scaling uses gain and bias for adjustment. Set the gain and bias values correctly.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
V/f
CL-V/f
OLV
CLV
AOLV
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
V/f
CL-V/f
OLV
CLV
AOLV
Sets the DriveWorksEZ digital output. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Sets the digital output for the DriveWorksEZ DO-A3 option card. Refer to the DriveWorksEZ online manual for more information.
V/f
CL-V/f
OLV
CLV
AOLV
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which function to inversely
output.
Table 12.64 MFAI Setting Values
Ref.
936
936
936
937
937
937
937
938
938
938
938
939
939
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
Setting
Function
Value
E
Motor Temperature (PTC Input)
F
Not Used
10
Forward Torque Limit
11
Reverse Torque Limit
12
Regenerative Torque Limit
13
Torque Reference / Torque Limit
14
Torque Compensation
15
General Torque Limit
16
Differential PID Feedback
1F
Not Used
30
DWEZ Analog Input 1
31
DWEZ Analog Input 2
32
DWEZ Analog Input 3
12.8 H: Terminal Functions
Ref.
939
939
939
940
941
941
941
941
941
941
941
942
942
12
929

Advertisement

Table of Contents
loading

Table of Contents