YASKAWA GA800 Technical Reference page 289

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

R/L1, R1/L11
Model
S/L2, S1/L21
T/L3, T1/L31
3/0 × 2 × 2
T568
-
-
4/0 × 2 × 2
T605
-
-
-
T720
250 × 2 × 2
-
*1
For use with PANDUIT Corp. heat-shrinkable tubing HSTT-series or an equivalent UL-recognized heat-shrinkable tubing rated 600 V
minimum.
UL Compliance
Install one of the types of short circuit protection devices to comply with UL 508C. Yaskawa recommends connecting
semiconductor protection fuses. Refer to
291, and
6-Phase/12-Pulse 400 V Class on page 292
devices.
• Semiconductor Protection Fuse
– When you use semiconductor fuses as UL listed drive protection, the drives and fuses must be in the same
enclosure.
– Where multiple semiconductor fuse ratings are listed for a single drive, Yaskawa recommends a fuse with a large
rated current for applications with repeated loads of approximately 150%. You can use smaller semiconductor
fuses (than what is listed) of the same manufacturer and series. Please note that this can decrease the life of the
fuses.
• Non-Semiconductor Fuse
– Maximum CC, J, T, RK1 or RK5 fuse rating is 175% of the Normal-Duty drive full load output amp (FLA)
rating.
– When you use class CC, J, or T fuses as UL listed drive protection, models 4371 and larger have the same
minimum enclosure volume requirements as MCCBs.
– Install Class RK1 or RK5 fuses into a ventilated enclosure with a minimum enclosure volume shown in
5.20,
Table
5.21, and
Table
• Molded-Case Circuit Breaker (MCCB)
– Maximum MCCB rating is 200% of the Normal-Duty drive full load output amp (FLA) rating.
– When you use MCCBs, install the drive into a ventilated enclosure with a minimum enclosure volume shown in
Table
5.20,
Table
5.21, and
Note:
Yaskawa recommends current limiting MCCBs.
• Short Circuit Current Rating (SCCR)
The maximum SCCR provided by drive and fuse, or drive and MCCB combinations in this document, is 100,000
RMS symmetrical amps.
– 240 V Cass drives: Use the protection specified in this document to prepare the drive for use on a circuit that
supplies not more than 100,000 RMS and not more than 240 Vac when there is a short circuit in the power supply.
– 480 V Class drives: Use the protection specified in this document to prepare the drive for use on a circuit that
supplies not more than 100,000 RMS and not more than 480 Vac when there is a short circuit in the power supply.
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Recomm. Gauge (AWG, kcmil)
U/T1
V/T2
W/T3
-
3/0 × 4P
4/0 × 4P
-
-
4/0 × 4P
300 × 4P
-
-
4/0 × 4P
-
300 × 4P
Three-Phase 200 V Class on page
for recommended fuses and alternative short circuit protection
5.22.
Table
5.22.
-
+3
3/0 × 4P
-
-
-
-
4/0 × 4P
-
-
-
-
4/0 × 4P
-
-
-
-
290,
Three-Phase 400 V Class on page
5.3 UL Standards
Crimp Terminal
Model
*1
-
S3/0-12R-5
-
S4/0-12R-5
2/0
S2/0-12R-X
-
S4/0-12R-5
LCA300-12-X
-
LCAX300-12-6
2/0
S2/0-12R-X
-
S4/0-12R-5
-
S250-12R-5
LCA300-12-X
-
LCAX300-12-6
Table
289
5