YASKAWA GA800 Technical Reference page 864

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.7 F: Options
Register
No. (Hex.)
Output frequency or frequency reference (Drive Status Bit 4: ON) (Drive
15EC
3)
15ED
Drive Status (Drive 4)
Output frequency or frequency reference (Drive Status Bit 4: ON) (Drive
15EE
4)
Slave Address for Reg. Access + During MEMOBUS process & ErrCode
bit 0
00H: MEMOBUS/Modbus Communication Complete
bit 1
02H: Register number not registered
bit 2
21H: Upper/Lower Limit Fault
bit 3
22H: Write Mode Error
bit 4
23H: Write performed during Uv
bit 5
24H: Write performed while writing parameter settings
bit 6
FFH: During MEMOBUS/Modbus Communication
bit 7
15EF
Slave address
0: Broadcast Messages (MEMOBUS)
bit 8
1: Drive 1
bit 9
2: Drive 2
bit A
3: Drive 3
4: Drive 4
5: Broadcast Messages (run command and frequency reference)
bit B - F Reserved
15F0
Register number
15F1
Data (write register)
F6-01: Communication Error Selection
No.
Name
(Hex.)
F6-01
Communication Error
Selection
(03A2)
0 : Ramp to Stop
The drive ramps the motor to stop in the deceleration time. Fault relay output terminal MA-MC turns ON, and MB-
MC turns OFF.
1 : Coast to Stop
The output turns off and the motor coasts to stop. Fault relay output terminal MA-MC turns ON, and MB-MC turns
OFF.
2 : Fast Stop (Use C1-09)
The drive stops the motor in the deceleration time set in C1-09 [Fast Stop Time]. Fault relay output terminal MA-MC
turns ON, and MB-MC turns OFF.
3 : Alarm Only
The keypad shows bUS and the drive continues operation at the current frequency reference.
Note:
Separately prepare safety protection equipment and systems, for example fast stop switches.
The output terminal set for Alarm [H2-01 to H2-03 = 10] activates.
4 : Alarm (Run at d1-04)
864
V/f
CL-V/f
OLV
CLV
AOLV
Sets the method to stop the motor or let the motor continue operating when the drive detects bUS
[Option Communication Error].
Description
The unit of measure changes when o1-03 changes.
Outputs when:
• Normal operation: Output frequency
• Drive detects Frequency Reference Setting Fault: Frequency reference when the error
occurs
Clears the value when the drive detects a communication error or communication stops.
Refer to "15E7: Drive Status (Drive 1)" for more information.
The unit of measure changes when o1-03 changes.
Outputs when:
• Normal operation: Output frequency
• Drive detects Frequency Reference Setting Fault: Frequency reference when the error
occurs
Clears the value when the drive detects a communication error or communication stops.
Note:
If you change the access command before the MEMOBUS/Modbus access flag turns on,
the drive will not do the command from before.
Description
OLV/PM AOLV/PM CLV/PM EZOLV
OLV/PM
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Default
(Range)
1
(0 - 5)