H: Terminal Functions; H1: Digital Inputs - YASKAWA GA800 Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800:
Table of Contents

Advertisement

12.8

H: Terminal Functions

H parameters are used to assign functions to external input and output terminals.

H1: Digital Inputs

H1 Parameters set the MFDI terminal functions.
H1-01 to H1-08 Terminal S1 to S8 Function Selection
The drive has 8 MFDI terminals. Refer to
No.
H1-01
Terminal S1 Function Selection
H1-02
Terminal S2 Function Selection
H1-03
Terminal S3 Function Selection
H1-04
Terminal S4 Function Selection
H1-05
Terminal S5 Function Selection
H1-06
Terminal S6 Function Selection
H1-07
Terminal S7 Function Selection
H1-08
Terminal S8 Function Selection
*1
The value in parentheses identifies the default setting when you set A1-03 = 3330 [Initialize Parameters = 3-Wire Initialization].
Refer to the
Table 12.55
and use H1-xx [MFDI Function Select] to set the function.
Setting Value
*1
0
3-Wire Sequence
1
LOCAL/REMOTE Selection
2
External Reference 1/2 Selection
3
Multi-Step Speed Reference 1
4
Multi-Step Speed Reference 2
5
Multi-Step Speed Reference 3
6
Jog Reference Selection
7
Accel/Decel Time Selection 1
*1
8
Baseblock Command (N.O.)
*1
9
Baseblock Command (N.C.)
A
Accel/Decel Ramp Hold
B
Overheat Alarm (oH2)
C
Analog Terminal Enable Selection
D
Ignore Speed Fdbk (V/f w/o Enc)
E
ASR Integral Reset
F
Not Used
10
Up Command
11
Down Command
*1
12
Forward Jog
*1
13
Reverse Jog
14
Fault Reset
YASKAWA SIEPC71061737D GA800 Drive Technical Reference
Table 12.54
Table 12.54 MFDI Default Settings and Functions
Name
Table 12.55 MFDI Setting Values
Function
Reference
885
886
886
886
887
887
887
887
887
888
888
888
888
888
888
889
889
890
891
891
892
for drive default settings and functions.
Default
*1
40 (F)
Forward RUN (2-Wire)
*1
41 (F)
Reverse RUN (2-Wire)
24
External Fault (NO-Always-Coast)
14
Fault Reset
*1
3 (0)
Multi-Step Speed Reference 1
*1
4 (3)
Multi-Step Speed Reference 2
*1
6 (4)
Jog Reference Selection
8
Baseblock Command (N.O.)
Setting Value
*1
15
Fast Stop (N.O.)
16
Motor 2 Selection
*1
17
Fast Stop (N.C.)
18
Timer Function
19
PID Disable
1A
Accel/Decel Time Selection 2
1B
Programming Lockout
1E
Reference Sample Hold
*1
20 to 2F
External Fault
30
PID Integrator Reset
31
PID Integrator Hold
32
Multi-Step Speed Reference 4
34
PID Soft Starter Disable
35
PID Input (Error) Invert
3E
PID Setpoint Selection 1
3F
PID Setpoint Selection 2
*1
40
Forward RUN (2-Wire)
*1
41
Reverse RUN (2-Wire)
*1
42
Run Command (2-Wire Sequence 2)
*1
43
FWD/REV (2-Wire Sequence 2)
44
Add Offset Frequency 1 (d7-01)
12.8 H: Terminal Functions
Function
Function
Reference
892
892
893
893
894
894
894
894
895
895
896
896
896
896
896
896
897
897
897
897
898
12
881