Analog Output Objects; Analog Value Objects - YASKAWA BACnet/IP JOHB-SMP3 Technical Manual

Ac drive option
Hide thumbs Also See for BACnet/IP JOHB-SMP3:
Table of Contents

Advertisement

Object ID
(Network Display, if Different)
(Drv Anlg In 3 Level)
Bypass Analog Input 1 Level
*2
AI4
(Byp Anlg In 1 Level)
AI6
Display Format o1-03
AI7
AI8
Inverter Model o2-04
AI9
*2
AI10
Motor Current UB-01
*2
AI11
*1
Not available on all drives. Refer to the Technical Manual of your drive, and check if the Modbus register of the applicable object
exists.
*2
Available on bypasses only.

Analog Output Objects

Object ID
(Network Display, if Different)
Drive Analog Output 1 Level
AO1
(Drv Anlg Out1 Level)
Drive Analog Output 2 Level
*1
AO2
(Drv Anlg Out2 Level)
*1
Not available on all drives. Refer to the Technical Manual of your drive, and check if the Modbus register of the applicable object
exists.

Analog Value Objects

Object ID
(Network Display, if Different)
Drive Operation Command
*1
AV1
(Operation Cmd)
AV2
AV3
Drive Multi-Function Output Command
(MF Output Cmd)
• Bit 0: Multi-FunctionDigital Output 1
(terminal M1-M2)
• Bit 1: Multi-FunctionDigital Output 2
(terminal M3-M4)
• Bit 2: Multi-Function Digital Output 3
(terminal M5-M6)
(Z1000U: MD-ME-MF)
• Bit 3: Reserved
AV4
• Bit 4: Reserved
• Bit 5: Reserved
• Bit 6: Enables the function in bit 7
• Bit 7: Fault Contact Output (terminal
MA-MB-MC)
• Bit 8 to F: Reserved
Note:
When using AV4, do not use BO1 to
BO3 or BV12.
Drive Reference Select Command
(Reference Select Cmd)
AV5
• Bit 0: Reserved
• Bit 1: PID Setpoint Input
YASKAWA SIEP C730600 0MA BACnet/IP Technical Manual
Object Name
Modbus Register (Hex.)
Scale Format b5-20
Rated Current n9-01
Contactor Voltage
Object Name
Modbus Register (Hex.)
Drive Terminal FM
(set H4-01 = 0)
Drive Terminal AM
(set H4-01 = 0)
Object Name
Modbus Register (Hex.)
Frequency Cmd
PI Setpoint Cmd
Range
8795
0 - 100.0
0502
0 - 65535
01E2
0 - 65535
0508
0 - 65535
0 - 6553.5 (for drives
rated higher than 11
kVA)
05D0
0 - 655.35 (for drives
rated 11 kVA or lower)
8780
0 - 655.35
8790
0 - 65535
Range
0007
0 - 100.0
0008
0 - 100.0
Range
0001
0 - 65535
0002
0 - 600.00
0006
0 - 100.00
0009
0 - 255
000F
0 - 32767
7 BACnet/IP Objects Supported
Unit
PV Access
%
-
-
-
A
A
V
Unit
PV Access
%
%
Unit
PV Access
Bitmap
Determined by o1-03
%
Bitmap
Bitmap
R
R
R
R
R
R
R
C
C
C
C
C
C
C
25